How to check gas pressure on water heater
White Rodgers gas control valve
White Rodgers Mechanical gas control
Intellivent gas control valve
Intellivent gas control used on some models of Power Vent heaters
Check gas pressure on water heater:
Buy
Gas Manometer, Gauge, Natural Gas, Propane, 0-35" W.C,
Yellow jacket manometer

1) Quick assessment of gas pressure
Watch what appliances do when adding load. If appliances stop working correctly when another gas appliance is activated, it implies low gas pressure. This observation can be done without equipment.

2) Supply gas pressure
Supply gas pressure, or line pressure checks are measured before the gas control valve and as close to the water heater as possible.
''Commercial and residential gas water heaters and boilers are design-certified to operate
with a maximum inlet gas pressure. To identify the maximum inlet gas pressure, refer to
the labeling on the appliance and/or gas control/valve. For reference, industry standard is
14” w.c. (1/2 psi). ''
"The minimum permissible gas supply pressure for the purpose of incoming gas supply to water heater is 1.0" water column (.25kPa) above the operating manifold pressure. See the rating plate and combination gas control for the manifold pressure and gas type. The maximum permissible gas supply pressure is 14.0" water column (3.5kPa) for natural gas and liquefied petroleum gases/propane gas.
"The Gas Control is designed for a maximum line pressure of 14.0" w.c. and a minimum line pressure of 1.0" w.c. over the water heater’s rated manifold pressure.
Line pressure must be checked with the main burner on and off to assure proper readings."
If line pressure is low: increase gas pressure regulator, or call gas company.
If line pressure is high, add gas pressure regulator, or call gas company.

Pressure rating is shown on water heater label
Check rating plate (label) located on side of water heater  for gas pressure rating
Typically, a propane heater will be higher than natural gas.
Line pressure is pressure on incoming gas line. Label shows max inlet or line pressure as 14.0" w.c.
Manifold pressure is gas pressure from gas control valve to burner. Label shows 4.0" w.c. to 5.0" w.c. for manifold pressure.

If the burner and/or pilot do not function, service checks for gas pressure, thermocouple output, magnet assembly and ECO are to be performed. If these check OK, the gas valve may be faulty."

"MANIFOLD PRESSURE TESTING
(this procedure assumes a maximum line pressure of 14.0" w.c.)
Step 1. Set gas valve to “OFF” position.
Step 2. Remove pressure tap plug located on the bottom of gas control valve (or side of Intellivent gas valve) and install pressure tap.
Step 3. Connect manometer to pressure tap.
Step 4 Follow lighting instructions and light main burner and observe manometer reading.
Step 5 Proper operating range for natural gas is 4.0 ±0.5" W.C. For intellivent 3.5 to 4.0" W.C.
Proper operating range for L.P. gas is 10.0 ±0.5" W.C.
Step 6 If pressure is OK, set gas valve to “OFF” remove manometer and pressure tap and replace pressure tap plug. Check for gas leaks before placing water heater back in operation.
If manifold pressure is high, check if burner orifice is correct size.
If orifice is correct and burner parts are clean, and pressure still measures out of range by +/- .3 inch, then go to next steps based on type of gas control valve.

Image above shows bottom of Honeywell gas control valve
For White Rodgers Intellivent and both types Honeywell electronic controls, the manifold pressure is not adjustable. If manifold pressure is outside the range shown in step 5, the gas control valve must be replaced.
For White Rodgers mechanical control, the manifold pressure is not adjustable. If manifold pressure is outside the range in step 5, the gas control valve must be replaced.
For Robertshaw mechanical control, the manifold pressure is adjustable, proceed to step 7 for adjustment procedure
Step 7 While burner is in operation, remove regulator access cap to expose the regulator adjusting screw. With small screw driver, rotate adjusting screw clockwise to increase pressure and counter clockwise to decrease pressure.
Step 8 Replace regulator access cap, set gas valve to “OFF”. Remove manometer and pressure tap and replace pressure tap plug. Check for gas leaks before placing water heater back in operation."
Buy
Gas Manometer, Gauge, Natural Gas, Propane, 0-35" W.C,
Yellow jacket manometer
Manometer
Gas pressure regulator
Resources:
Bradford white service manual Pg 15
Intellivent service manual
Compare gas controls, with service manuals
Gas pressure regulatorGas supply pressure is Low or High
If line pressure is low: increase gas pressure regulator, or call gas company.
If line pressure is high, add gas pressure regulator, or call gas company.

Buy
Manometer
Gas pressure regulator

Gas pressure regulatorGas supply pressure is Low or High
Incoming gas pressure too high
''In the event an installation site has been exposed to inlet pressures above the ratings listed on the product and/or the gas control/valve, the gas control/valve must be replaced.
Service/gas technician must inspect the entire appliance with focus on, but not limited to: burners, combustion chambers, heat exchangers and venting. In some cases, as determined by the qualified service/gas technician, the appliance may need to be replaced entirely.
Suspicion that an installation site has been exposed to excessive inlet gas pressure would require following the directions noted above.
Prior to installing the new gas control/valve and/or appliance and placing it back into service, the source of the excessive pressure must be identified and corrected by service/gas technician.''

"CHECKING GAS INPUT on AO Smith GCN-75 (75 gallon, 75,100 BTU) and GCN-100 (98 gallon, 75,100 BTU)

checking gas input
With this specific AO Smith 75,100 BTU heater in operation, determine whether it is receiving the full rated input of gas.

This may be done by timing the gas meter and measuring gas pressure with a gauge or manometer.
When the heater is operating at full capacity (full gas input) it should consume approximately 1 cubic foot of gas in the time shown in Table 4. (applies only to this model heater)


Use the formula on right to “clock” the meter.
Be sure that other gas consuming appliances are not operating during this interval.
Compare the actual input rate to that given on the heater’s rating plate.
In the example, the full input rate should be 75,100 Btu/Hr for natural gas."

Resources:
GCN-75/100 Manual P25
GCN-75/100 Spec sheet
Back to 10 things for troubleshooting water heater
Icon gas valve
For atmospheric vent models
Range Low 55° - very hot 160°
Average bath 110°F, typical water heater temp 120°
ECO limit 199° F, ECO trips, gas valve fails
TP release water at 170°
All calibrations are approximate
Severe scalding risk over 135°
To reset gas control, rotate dial to OFF, wait 10 minutes for gas to clear. Then relight.
Buy
Reliance/ Honeywell gas control
American / Honeywell gas control
Kenmore water heater gas valve
Craftmaster/ Whirlpool
Bradford White
AO Smith

Honeywell gas control at Amazon
American / Honeywell gas control at Amazon
Honeywell gas valve for propane
Honeywell natural gas valve
Reliance NG at Amazon
Reliance LP at Amazon
Kenmore water heater gas valve
Gas water heater timer fits this valve
Replacement instructions
How to test & replace Honeywell/ pdf
WT8840 replacement manual
How to replace Honeywell gas control valve

Resources WV8840/ WT8840:
Typical installation manual
Typical installation manual/ low NOx
Adjust temp on Honeywell gas valve
Error codes WV8840 series
Error codes WV8840 series
Error codes WT8840
AO Smith service handbook
Service handbook
State Error code/ troubleshoot/ service manual/ FVIR
Bradford White service manual
Error light blinking 4 times
How to light water heater
How to light water heater/ pdf
How to light Whirlpool energy smart

WT8840 product overview models
WT8840 gas valve manual and troubleshoot

How to replace gas control valves
How to test gas control valve

How to install gas water heater

For power vent and flue dampered models
Range Low 90° - very hot 160°
Average bath 110°F, typical water heater temp 120°
ECO limit 199°F, ECO trips, gas valve fails
Average bath 110°F
ECO limit 199°F
TP release water  at 170°
Buy
Example Honeywell gas control valve at Amazon
Reliance NG at Amazon
Replacement instructions
How to replace water heater gas valve

Resources:
Flue dampered service manual/ atmospheric
Flue dampered/general install and troubleshoot
Dampered troubleshoot codes
Dampered error codes
Dampered error codes
Induced draft troubleshoot codes
Example dampered install manual2

Example power vent install manual
Example power vent install manual
Example power direct vent install manual
Adjust temperature/ error codes on Honeywell
How to light Honeywell gas valve
Error codes and troubleshoot chart
Error codes
Error codes
Icon gas valve error codes

AO Smith service handbook
Bradford White power vent service manual 1
Bradford White power-vent service manual 2
Bradford power-direct-vent service manual
Condensing power vent service manual
Test gas control/ from BW service manual
Sequence of operation
How to clean burner

Safety
Water heater safety precautions
Water heater precautions/ pdf
Gas-water-heater-Safety-Precautions
Gas valve safety
Thermal expansion
Insulation blanket

For power vent models
Range Low 80° to Hot 150°
Error C flashes at 160°
Buy
Buy Intellivent gas control at Amazon
White Rodgers/ Rheem Intellivent gas control
AO Smith intellivent
AO Smith Intellivent at Amazon
AO Smith White Rodgers at Amazon

Replacement instructions
How to replace water heater gas valve
Resources:
How to light water heater
Typical installation manual
Sample installation manual
Example install manual
Ultra low nox power vent manual
Error codes and adjust temp on Intelli-vent
AO Smith Intellivent troubleshoot and FV test
Troubleshoot Intellivent/ pdf
FVIR intellivent troubleshoot .pdf
Intellivent service manual TC-048 R6
Sequence of operation and service brief
Intellivent wiring
Power direct vent troubleshoot
Status codes and troubleshoot/ condensing
How to reset intellivent
For resetting controller:
Method A... After the unit has been off for at least a minute, plug it in, turn on switch; within a few seconds, depress both arrow buttons on controller, and hold them until the left light begins to blink.  Release them, and within a few seconds, push those arrow buttons in the following sequence:  L/R/L/L/R/L/R/R.  This should reset the controller.
Method B... after FV event on AO Smith
1. Turn off power to water heater for 10 seconds.
2. Restore power to water heater.
3. Within 10 seconds of restoring power, press the two temperature adjust buttons simultaneously until the left (green) “Vacation” LED begins to blink (approx. 5 second delay). Once the Vacation LED begins to blink, release both buttons.
4. Again, within 10 seconds, press both temperature adjust buttons simultaneously until
Vacation LED is on steady (approx. 5 second delay).
5. Release two buttons, the  microcomputer will clear the FVS lock-out and normal
operation will then be restored.
gas valve setting
Larger image
Buy
Gas control valve thermostats at Amazon
Gas water heater thermostats at Amazon
Rheem gas control valve at Amazon
Gas control valve at Amazon
Camco White Rodgers at Amazon
Gas water heater timer fits this valve
Replacement instructions
How to replace water heater gas valve
Resources:
Service manual
Service manual 2
Service manual 3
Operation and safety
How to light water heater/pdf
General troubleshoot manual /pdf
White Rodgers gas control valve replacement pdf
Power vent water heater issues
Magnet testing
Test thermocouple
Gas valve testing
How to light gas water heater
White Rodgers NG replace, install, set temp

Robert Shaw
Buy
Gas water heater thermostats at Amazon
Robert Shaw natural gas
Robert Shaw propane gas
Replacement instructions
How to replace water heater gas valve

Resources:
Robert Shaw models
Robert Shaw/ Unitrol troubleshooting/ pdf
General troubleshoot/ pdf
General troubleshoot manual /pdf
How to light water heater/pdf
Magnet testing
Test thermocouple
Gas valve testing
Operation and safety
Recalibrate gas control/ pdf
How to light gas water heater
Adjust pilot on unitrol gas control valve
How to test White Rodgers gas valve p14
How to test Honeywell Icon gas valve p23
How to test Robertshaw gas valve p14
Robert shaw gas control valve
Robert Shaw 120Volt input gas control valve
Wiper Control and Gas Valve assembly
Triangle pointed upward is 120 degrees F
Replacement for Rheem power vent/
Buy
Rheem wiper SP20123A thermostat KIT
Wiper SP20123B valve/ no thermostat


Resources
Larger image
Error Codes and troubleshoot
Guardian power vent Robert Shaw error code
Rheem parts list
American power flex parts
General manual with lighting instructions
Replace water heater gas control and FV
Check pressure switch, blower, gas control
Sequence of operation
How to light water heater
To reset: turn the red control knob on and off 6 times within 30 seconds to reset the board.
What you need for operation of gas water heater.
General troubleshoot
1) Basic parts and operation
2) Adequate incoming air supply ... issues: closed doors, tightly insulated house, very hot attic.
3) Adequate air supply getting to burner... issues: dirty vent screen, dirty environment, maintenance.
4) Thermal cutoff  ... TCO ... issues: failed part, maintenance, vent.

5) Flammable vapor lockout .... issues: exposure to vapors, bad FV sensor, failed FV system,
6) Fuel supply to gas valve thermostat ... natural gas and propane are different ... issues: wrong gas, low pressure, moisture in pipe, undersized gas meter, supply line too small for BTU rating.
7) Gas valve thermostat regulates fuel supply ... issues: not enough gas, failed thermostat, failed gas control valve.

8) Fuel supply from thermostat to burner ... issues: maintenance, thermocouple-thermopile, gas control valve.
9) Clean and replace burner ... issue: periodic maintenance requires burner inspection, cleaning, and possible replacement

10) Functioning thermopile-thermocouple-pilot light ... issues: misalignment, failure of part.
11) Ignition of fuel supply by pilot light or hot surface igniter ... issues: pilot light, piezo igniter, electrode.

12) Power vent water heater troubleshoot ... issues: pressure switch, blower, blower sequence from gas control, outlet polarity
13) Venting combustion byproduct .... issues: vent in disrepair, other vents in house drawing air

14) Misc troubleshoot manuals

Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Install and troubleshoot garbage disposal Waste King disposal
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook