Home
Search waterheatertimer.org / all results
Search using Find button  

 Tweet button  
Difference between Delta and Wye
WYE and Delta are terms used to describe commercial 3-phase wiring configuration for transformers used in the electric grid


Fig 1-1 WYE
3 coils wired in parallel
120-208 volt 4-wire 3-phase with ground
3 transformer coils (windings) wired in WYE configuration :
The 3 coils are wired in parallel with each other.
Amperage on each line equals amperage on each coil.
Phase Voltage between Hot and Neutral is same for each line.

When windings are connected wye, the voltage between any two lines (line to line) will be 1.732 times the phase voltage (line to neutral), and the line current will be the same as the phase current.
The common point of the three windings is called the neutral because equal voltages exist between this point and any of the three phases.

Resource
What is 208 volt
What is 277 volt

Fig 1-2 Delta
3 coils wired in series ... end to end
120-208-240 volt 4-wire 3-phase with ground
3 transformer coils (windings) wired in Delta configuration :
The 3 coils are wired in series with each other, like batteries end to end.
Amperage on each line is 1.732 times the amperage on each coil.
Higher amperage means more amps per volt, giving more power per volt.
Each line carries the same voltage.

When transformers are connected delta, the line current will be 1.732 times the phase current, and the voltage between any two will be the same as that of the phase voltage.
Resources
Transformer Basics pdf
3-phase power math .pdf
What is high leg delta

In a wye connected system, the line voltage is higher than the phase voltage by a factor of the square root of 3 (1.732).
Line current and phase current are the same in a wye connection.
Source: 3-phase power math .pdf

In the delta connection, line voltage and phase voltage are the same.
The line current of a delta connection is higher than the phase current
by a factor of the square root of 3 (1.732)
Source: 3-phase power math .pdf
Delta transformer calculations .pdf
Transformers
Transformers are used throughout the grid to accomplish different objectives. Transformers control the inverse relationship between voltage and amperage. Raise the voltage and the amperage goes down. Lower the voltage and the amperage goes up.
For example, wires leaving the power plant might carry 500,000 volts. The high voltage means low amps and low heat on the wire which allows economic  long-distance transmission of electricity. While high voltage is good for transmission, the switchgear and wiring needed for 500,000 volts is too large, expensive and dangerous for ordinary use inside a home or building.
Using transformers, the power company can change the volt-amp ratio. The result is homes and buildings receive low volt, high amp power. It works nicely because 120-240-208-277-480 volt power can be safely controlled by small switches, relays, cell phone chargers etc contained within steel and plastic enclosures, while the amperage (heat) is controlled by circuit breakers and then distributed to outlets, switches, motors, lights etc using correctly sized wire to match amp rating of breaker.

WYE and Delta wiring configurations are one method of using a transformer to reach a volt-amp objective.
Before going farther, it's important to describe how a transformer works.
Transformers work on a basic principle of magnetic induction where applying electricity to one coil of wire creates a magnetic flux that will energize the other coil of wire with electricity. How transformers work pdf
Inside a transformer are two coils of wire called the primary and secondary coils. Each coil is wrapped around a laminated iron core or more efficient amorphous metal core. The metal core is shared by both coils, but both coils of wire are 'insulated' from each other. They are electrically separated. There is no wire in common between the coils, only the metal core is shared.

Having different numbers of turns of wire, or varying the turns ratio, on each coil will raise or lower voltage. Different voltages can be achieved throughout the grid by varying the number of turns on the primary and secondary coils.

The power company connects 4500-7200 volts from the distribution lines to the primary coil. This produces voltage on the secondary coil. Different transformers are selected depending on the voltage specified for end user. The end user's wires are connected to the secondary coil and power is routed into the main breaker panel.

Illustration shows WYE-WYE electric service
Primary side of transformers is wired in WYE
Secondary or customer side of transformers is wired in WYE
This is typical of WYE, 4-wire, 3-phase service
Common voltages include: 120-208 and 277-480
120 and 277 are the Phase voltages measured between 1 Hot and Neutral
208 and 480 are the Line voltages measured between 2 Hot wires

Illustration shows WYE-Delta electric service.
Primary side of transformers is wired in WYE
Secondary or customer side of transformers is wired in Delta
This is typical of High-Leg Delta, 4-wire, 3-phase service
Common voltages include: 120-208-240, and sometimes 240-418-480
120-208 are the Phase voltages measured between 1 Hot and Neutral
240 is the Line voltage measured between 2 Hot wires
Figures 1-1 and 1-2 above are representation of wiring for WYE and Delta on the secondary side of three transformers.
Typical 3-phase service has 3 secondary coils. There are variations (not shown on this page) called Open WYE and Open Delta etc that have 2 coils.
The actual appearance of wiring is different than the representations above. For example, the transformer coils do not actually touch each other. Instead they are connected by a wire.

Figure 1-1 WYE represents each transformer coil as a zig-zag line.
WYE (star) transformer coils (windings) are wired together to form the Neutral wire. There is 1 common point shared by each of the 3 coils of wire as shown in Figure 1-1. The common point gives rise to the Neutral wire. The other end of each coil gives rise to the 3 Hot wires.
Measuring voltage from the center point to end of any coil is called the phase voltage. This can be seen in Fig 1-1 as 120 volts. Other WYE services can have different voltages depending on the turns ratio selected for the service.
The voltage measured between any 2 Hot wires is known as the line-to-line voltage or simply as the line voltage. This can be seen in Fig 1-1 as 208 volts.

In a wye connected system, the Hot wire to Hot wire line voltage is higher than the phase voltage by a factor of the square root of 3 (1.732). So 120 volts x 1.732 = 208 volts.
In a wye-connected system, phase amps (current) and line amp are the same.

Fig 1-2 Delta represents each transformer using four uuuu's.
>Delta transformer coils are wired end to end. The Neutral wire if present is achieved by tapping into center of 1 coil.
'Line voltage and phase voltage are the same with Delta. If you measure Hot wire to Hot wire, you get same voltage as measuring both ends of one coil. However the amps vary between line voltage and phase voltage. Unlike Wye where phase and line voltage stay the same, with Delta, the line amperage is higher than the phase amperage. If phase amperage measure across one coil is 10 amps. the line amperage measured across two Hot wire is 10 amps x square root 3 or 1.732 = 17.32 amps.
As the generator spins, and voltage on each wire rises and falls, each Delta coil is energized at different times. At any given time, two of the three coils are energized. This adds extra current when measuring between the Hot wires.'
Delta has lower amps/ meaning less heat.
For example many transformer banks are wired Delta on the Power company or Primary coils, and Wye on the customer or secondary coils. The reason for this: the distribution voltage connected to primary side can be 4500-7900 volts, and using delta configuration means lower amps which means the manufacturer can use smaller wires on the primary side coils and save money, yet still deliver full power to the customer.
Materials used for the power grid are a balance of cost, safety, and function.
Star-Delta (WYE-delta) is also a configuration used for motor starter timers, such as a star-delta timer. With motors, they consume more amperage to start. To reduce the expense and heat, the motor is started with the star or wye configuration, and after the motor starts, the circuit is switched to delta for higher efficiency.

Why use 3-phase
"The horsepower rating of three-phase motors is about 150% greater than for single-phase motors with a similar frame size. The power delivered by a single-phase system pulsates, and the power falls to zero three times during each cycle. The power delivered by a three-phase circuit pulsates also, but it never falls to zero. In a three-phase system, the power delivered to the load is the same at any instant. This produces superior operating characteristics for three-phase motors."*
*3 phase circuits with basic math .pdf
How to identify transformer wiring
What is 3-phase
How to wire 3-phase
3-phase timer
Why do they use a combination of Wye and Delta configurations?
"The four most common three-phase transformer configurations are wye-wye, delta-delta, wye-delta, and delta-wye configurations. Each configuration presents different characteristics.
WYE-WYE or Delta-Delta configuration, the voltage, current, and phase relationships between the primary and the secondary are identical to the relationships found in a conventional single-phase power transformer. This means that the values of the line voltages and currents at the secondary are equal to those of the line voltages and currents at the primary."
WYE primary Delta secondary:
Line voltage relationship √3: 1
Line current (amp) relationship 1: √3
Phase shift 30° lag

Delta primary WYE secondary:
Line voltage relationship 1: √3
Line current (amp) relationship √3: 1
Phase shift 30° lead
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
stranded wire
600 volt 12 ga Stranded wire ot THHN wire is good for conduit with multiple wires ... but stranded cannot be installed under screw terminals on outlets, switches, timers etc without risk ... of heat causing splayed strands ....that come loose ... and begin to arc. Connect stranded to short piece of solid copper wire, and attach solid to screw terminal. Do not solder residential or commercial wiring.

Project wire, extension cords, thermostat, bell and automotive wire are not rated for residential or commercial wiring. Only wire maked 600 volt can be used for permanent household wiring.
Buy:
Southwire 600 volt stranded wire
Rolls of stranded wire
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI
Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric

How to install tankless recirculation


Install point of use water heater
Titan tankless

Contactors/ relays
Install and troubleshoot garbage disposal Waste King disposal
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Type 1 and type 2 surge protection surge protection
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook