How to wire Intermatic ET series timer

Larger image
ET1100 Series
ET1105 , ET1115, ET1125
24-hour / 20 and 30 amp models/ 28 set points/ 120-208-240-277Volt

1 channel or 2 channel operation ... so can control up to 2 loads, each with different program.
ET1125C offers SIM or IND for simultaneous or independent operation

Can switch 120V, 208V, 240V, 277V AC voltages ... Can also switch 12-24v AC or DC

Buy:
ET1125 timer
ET1725C timer
ET8215 timer

Resources
All ET1100 series timer models
Manual

Larger image
ET1700 Series/ 20 and 30 amp models/ 7-day 28 setpoints/ 120-208-240-277Volt

Does not offer SIM or IND
Can switch 120V, 208V, 240V, 277V AC voltages ... Can also switch 12-24v AC or DC

Buy:
ET1725C timer

Resources
All ET1700 series timer models
Manual
ET8015
ET8000 Series /7-day astronomic or programmable/ 1 or 2 channel/ 120-240-208-277Volt/

Does not offer SIM or IND
Can switch 120V, 208V, 240V, 277V AC voltages ... Can also switch 12-24v AC or DC

Buy:
ET8215 timer

Resources
All ET8000 series timer models
Manual

Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI
Select voltage Select voltage
Some timers have dip switches
Newest timers such as ET9000 automatically detect line voltage

The other ET series timers have a jumper for selecting voltage.
Jumper is located on back of timer.
By default, the timer arrives with jumper positioned for 240 volts (as illustrated).

Jumper position determines voltage for running clock, timer electronics, and magnetic switches.
The wiring terminals are dry and receive no power when power is applied to timer terminals 1 and 2.

To select 120Volt. Lift and move selector from 240V position to 120Volt position, and push selector down.
Select function using jumper
Some ET series models offer multiple function
ET70000 and 90000 functions are programmed, and timer can perform multiple functions throughout week.

Other ET models, such as ET1125 must be set for function ... and then timer stays in that function until jumper is moved again.

Default setting is SIM for simultaneous. Both relays turn on-off at same time.

Other functions include IND so that timer is able to control two separate loads, each with separate programming.
ET1125 timer wiring
Larger image

2 independent loads IND
Maximum combined load 30 amps.
Control Two 120V-277V loads with Hot and Neutral
Control Two 208-240Volt loads with Hot Line1 and Hot Line2
Wire terminals without jumper from supply voltage to control any voltage with relays.
Buy:
ET1125 timer
ET1725C timer
ET8215 timer
Resource:
ET1125 manual

Timer is shipped default 120Volts.
For 208,240,277 volt, set jumper located on back of timer.
Timer will automatically adjust for daylight savings timer, or can be disabled using jumper on back of timer.

For independent load operation (2 channel operation), move jumper from default SIM (simultaneous) to IND (independent.

Resource:
Color code for wire


ET1125 timer wiring

ET1125C offers SIM or IND for simultaneous or independent operation.

Example wiring shows how to switch one wire to turn 120V or 240V motor on and off.
Applies to 208V and 277V also.

ET series timer are not rated for 347V, 480V or 600V. If a suitable phase voltage is not available, then use buck-boost transformer.

This is the correct wiring for 120 volt if local codes prohibit switching the Neutral

Buy:
ET1125 timer
ET1725C timer
ET8215 timer
ET Series timers are rated for low voltage applications, both AC and DC.
The timer clock and relay fuction must be powered by 120V etc on terminals 1 and 2.

For example 120 V Hot and Neutral can be connected to terminals 1 and 2 to power the timer, then same 120V can be used to energize a 24VAC transformer, or 12-24VDC LED driver ... then switch the low voltage load using terminals 3-4 and 5-6.

By code, for safety, a shield must be installed between higher voltage lines and low voltage line ... especially where pool equipment is used.
Buy:
ET1125 timer
ET1725C timer
ET8215 timer
Example wiring shows how to switch 1 wire to turn 240V motor on and off

Buy:
ET1125 timer
ET1725C timer
ET8215 timer
ET1125 controls 3-phase ET1125 controls 480Volt load SIM
Use SIM or simultaneous, so both relays turn on-off at same time
Timer shipped default SIM setting
Change timer voltage selector to 277Volt.
ET1125 timer wiring ET1125 wiring 2 independent loads SIM
Both loads turn ON at same time
et1125 bell ringing ET1125 bell ringing SIM
All bells ring at same time
Program timer for Impulse or bell-ringing

Buy:
ET1125 timer
ET1725C timer
ET8215 timer
Change t104 timer to ET1725 Change wiring from T104 mechanical timer to ET1725
277 volt timer ET1125 controls 277Volt load SIM

For 3-phase 480V-277V:
Bring one 480V Hot and a Neutral wire to timer to produce phase voltage of 277V

Use SIM or simultaneous, so both relays turn on-off at same time
Timer shipped default SIM setting
Change timer voltage selector to 277Volt.
ET1125 manual

ET7015 7-day timer  
Five-terminal timer wired for 240 Volts

Selectable voltage 120 208 240 277

What do NO NC terminals mean?
NO NC terminals explained
:
NO terminal is Normally Open, this terminal receives power ONLY when timer turns on
NC terminal is Normally Closed, this terminal receives power and is on at all times EXCEPT when timer turns on, and then the NC turns off.

Larger image
3-phase timer 277Volt 277 Volt timer
277 Volt 3-pole contactor
277V 480V 3 Phase service with system Neutral
Buy:
90 amp 277V coil 3-pole lug terminals
75 amp 277V coil 3-pole lug terminals
30 amp 277V coil 3-pole
How to wire 3-phase timer

3-phase timer wiring
Intermatic GM40
Tork DTU40
GE 15207
Intermatic T104 and T174

Square D 277 Volt contactor at Amazon
ET 170 series manual
7 day programmable
Read manual to set jumpers for selectable voltage
Selectable voltage 120 208 240 277
Wiring
ET173C and ET174C have 6 terminals and wire same as Fig 1 shown above
ET175C has 5 terminals and wires same as Fig 6 shown below
ET270 series manual
7 day programmable
2 independent outlets
120Volt timer
2 channel timer with selectable voltage
Can operate 2 Loads with different schedule for each Load
Maintained or momentary bell-ringing contacts
Wiring
Read manual for specific wiring options
Wiring is similar to diagrams shown here but the 2-channel option complicates summary drawings.
ET1100 series manual
24 hour
14-ON and 14-OFF
Selectable voltage 120 208 240 277
Read manual for PUL and SIM jumper
2-second pulse for mechanically held contactor = PUL
Multiple Load simultaneously = SIM
Independent Loads = IND (ET1125 only)
Wiring
ET1105 has 4 terminals and is wired like Fig shown above
ET1115 has NO and NC terminals and is wired like Fig 6 shown below
ET1125 has 6 terminals and is wired like Fig 1 shown above
ET 8000 series manual
Astronomic dawn-dusk timer is not necessarily best choice for water heater timer
Selectable voltage 120 208 240 277 Wiring
ET8015 has 4 terminals and wire same as ET102 Fig 2 shown above
ET8215 ET has 6 terminals and wire same as Fig 1 shown above

ET8115 has NO NC terminals same as Fig 6 shown below
Many other wiring variations are possible

Intermatic 70815-71615 Manual
24 volt ET70815CR24 and ET71615CR24
Or selectable voltage ET70815CR and ET71615CR.
4 channel ET70615 or 8 channel ET70815.
24-Hour, 7-day, 365-day optional pulse, fixed switch, astronomic, interval, short-duration, timer with 8-year battery, with isolated NO and NC terminals that allow switching any voltage no matter which timer power voltage is selected.
Each channel can have different timing schedule.
Each channel can control any voltage, and voltage can be different for each channel.
Replaceable logic module
Wiring
Read manual for specific wiring options.
Wiring is similar to diagrams shown here but the 2-channel option complicates summary drawings.
ET70815CR ET70815CR24 Intermatic-et71615cr
Other ET timers.
ET series plug-in type timers by UPM
Paragon ET series
Grasslin ET616
Discontinued models
Intermatic ET104C
Larger image
ET104C Manual

ET104C discontinued at Amazon
Replace with EH40 240 volt 30 amp

Buy:
30 amp timers
ET104C water heater timer ET104C 240volts/ 1 load SPDT
ET104C has selectable voltage that is preset to 240Volts
Selectable voltage 120 208 240 277
Default voltage from factory is 240Volt

Same illustration applies to ET173 and ET174 7-day timers
If your timer has 4 terminals instead of 6, then same wiring applies, use diagram below

ET104 24-hour timer with 4-ON and 4-OFF per day
Buy ET1100 series for 24-hour 14-ON and 14-OFF per day
Intermatic ET104C ET104C 240volts/ 1 load SPST

ET104 has 6 terminals, and ET102 has four terminals
ET104C and ET102 have selectable voltage that is preset to 240Volts
Intermatic ET104C ET104C-wiring for 120 Volts ET104C 120volts/ 2 loads SPDT
ET104 has 6 terminals
How to wire to control 2 separate 120Volt loads

Factory default voltage is 240
Electricity leaves power plant Resource:
What is 3-phase electric: power plant to end user
See inside main breaker box
Basic house wiring
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker.

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
    
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Armored cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

Non metallic flexible cables must carry ground wire, but does not have hazard of short circuit causing injury from shock.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Armored cable
Southwire armored cable cutter
Non-metallic flexible conduit
Power whip
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but issues of insulation failure, lack of proper grounding, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems pose a risk to anyone working on electric power.

Buy:
Electrician tools kits
Klein tools
Tools kits
stranded wire
12 ga Stranded wire is good for conduit with multiple wires ... but stranded cannot be installed under screw terminals on outlets, switches, timers etc without risk ... of heat causing splayed strands ....that come loose ... and begin to arc. Connect stranded to short piece of solid copper wire, and attach solid to screw terminal. Do not solder residential or commercial wiring.
Buy:
Rolls of stranded wire

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistances and heat on wire and creates possible weak point.
Buy tools:
Wire strippers at Amazon
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

Use only solid copper wire, and no insulation under screw plate.

Tighten screw very tight against copper wire
Insdulation under screw plate
Larger image
Both wires MUST be same gauge
Straighten each wire

Max 2 wires under screw plate
Both wires same gauge

Larger image

Connect stranded and solid with wire nut and run jumper to screw plate.
Or add solder to stranded wire to make solid.
See example image

Use wire nut    
Push on wire connectors
Use push-on wire connectors

3 wires/ or different gauge wires

Join wires with wire nut or push-on connector
Run jumper to screw terminal.
Buy:
Push on wire connectors at Amazon
Red 3P connector (shown) for 10-14 gauge wire
Lever nuts for stranded wire at Amazon
Resource:
How to select and install wire connector

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook