How to install 3-phase timer

Electricians forum
Engineering toolbox
3-phase timer Buildings with 3-phase power also have Neutral wire used to power ordinary 120Volt outlets.

1) Use 120 Volt timer.

2) Install 3-pole contactor with 120Volt coil

3) Timer controls 120Volt coil.

4) 3-pole contactor turns 3-phase power ON-andOFF.

Examples of this timer:
Intermatic EH10 7-day programmable
Intermatic T101 24-hour analog
Repeat cycle timers
Dawn-dusk timer
365-day programmable timers
277Volt 24-hr analog timer
Example 3-pole contactor with 120Volt coil at Grainger

Example 3-pole contactor with 24Vac coil at Grainger

3-pole 204-244V contactor Grainger

Example 3 & 4-pole 120Volt coil at Zorro

Example 3 & 4-pole 24Volt coil at Zorro

Example 3 & 4-pole 480Volt coil atg Zorro

3-phase industrial timers


3 phase tiimer Some timers have dry load terminals.

1) Timer clock is 120 volt.

2) Timer relays are dry and receive no power from clock wiring.

3) This type of timer can be used to control 24Vac power from a transformer.

4) Install 3-pole contactor with 24Volt coil

5) Timer controls 24Volt coil.

5) 3-pole contactor points turn 3-phase power ON-andOFF.

Examples of this timer:
Intermatic GM series
Intermatic ET series



Intermatic ET series
Intermatic ET9000 timer can be programmed with 4000 set points over 365 day calendar year. Each day of year can be different. Each month can be different etc.


Example timers: select 3-phase timer
Help choosing programmable timer
Nema 1 enclosure: Indoor
Nema 3R 3nclosure: Indoor/outdoor
120Volt
EH10 7-day 120Volt programmable timer

Nema1
Programming steps and wiring appear on inside of timer door so they cannot be lost.
6 ON and 6 OFF programs per week.
Terminals 3 and 4 are dry, and can be used for 24Vac transformer and 24V coil contactor: Connect power to terminals 1 and 2. Do not install jumper wire between terminals 2 and 3. Connect wire from transformer to terminal 3. See illustration of dry terminal wiring scroll down to ET1725 timer.

AA battery located below timer buttons.
EH10 operating and programming manual
EH10 wiring

120Volt
T101 24-hour analog timer

T101R for indoor-outdoor
Replaceable trippers, Replaceable clock motor. Must be reset after power outage
1 Hour minimum on-off
T101 Manual
More wiring diagrams for T101
Wire T104 timer for 277 volts
277Volt
T104 24 hour analog timer

T104R for indoor-outdoor
Can be wired for 277 Volt or 440 volt. Clock wiring must be changed as shown in illustration, same as shown in manual.

Replaceable trippers, Replaceable clock motor. Must be reset after power outage
1 hour minimum on-off because of tripper thickness
T104 instruction manual
More wiring diagrams for T104

Larger image
ET1725 wiring
120 thru 277V
Intermatic ET1715 & ET1725 7-day timer

Can be set for 277 Volts

Default 120Volt.
Can be changed to 240V, 207V on back of timer
14 ON and 14 OFF programs
Two AAA batteries
ET1700 series manual
Intermatic ET1715CR timer
Larger image

Dry terminals:
Connect 24Vac transformer wires to 3-pole contactor

ET1725 wiring for 24 volt
GM40 timer wiring
Same wiring for 120/ 277V
Use diagram above to illustrate dry terminal wiring for 24Vac transformer
120-240-277V
Intermatic GM40 timer for 24 hour or 7-day

Can be set for 277 Volts

GM40 24-hour (15 minute time intervals)
GM40W 7-day (2 hour time intervals)
40 amp NO NC contacts
Dip switches to select voltage: Select between 120Volt, 240V, or 277Volt
Set dip switches before applying voltage
GM40 instruction manual
Sell sheet with model numbers
Sell sheet 2
GM40 timer

120V thru 277V
Intermatic GM40AVE programmable

20 set points
24 or 7-day
1 minute time intervals
120Volt thru 277Volt
Battery back-up
GM40AVE manual
GM40AVE sell sheet
Intermatic GM40AVE
FM1 wiring
GMX wiring
Larger image
120Volt
GMX series timer


24 hour (15 minute time intervals)
7-day (2 hour time intervals)
Simple, reliable FM1 timer module installed inside enclosure.
Reset after power outage
Nema 1 indoor
or Nema 3R outdoor enclosures
120V, 240V, 24V
GMX sell sheet with model numbers
Intermatic GMX series timer
Larger image
120Volt to 440Volt photo eyes

Control 3-phase using 120Volt timer with 4SP & 3SP relays

Same wiring applies to both timers shown
Intermatic T7401B timer
Larger image
120V or 277V

Intermatic T7401B 120Volt 7-day timer

Intermatic T7402 277Volt 7-day timer
T7000B Sell sheet

Minimum 2 hour ON-OFF
21 ON-OFF settings per week
T7041B wiring for 3-phase
Tork 7300 timer Tork 7300 24-hour Timer
3SP relays
120Volt clock motor
8-14 gauge wire
40 amp contacts
Single-phase -or- 3-phase 3-wire

Manual

Tork timers and manuals
3-phase timer
Larger image
Intermatic astronomic timer

Intermatic V45000 astronomic 24-hour dawn-to-dusk timer
3SP relays
120Volt clock motor
8-14 gauge wire
40 amp contacts
Single-phase -or- 3-phase 3-wire
Sell Sheet
Add time zone to end of model number
Instruction manual 120V

Intermatic timers and manuals

How to wire 3-phase outlets and surge protection

Cooper brand outlets
Wire color codes at Wikipedia
3-phase wiring
Line-to-line voltage = line to neutral x √3
3-phase has 2 varieties: 3-wire: three hot wires and no neutral, and 4-wire: three hot wires and a neutral

Types of phase wiring
3-phase wiring
Larger image
277 480 Three Phase WYE

480 volts across line-to-line

277 volts line-to-neutral

All Wye connections provide two voltages due to the common point or neutral connection.

Line-to-line voltage = 480V
Line-to-neutral voltage = 277V
277 Volt x √3 = 479.778 Volt

√3 = 1.7320
Voltages are higher or lower based on windings inside the transformer.
Power is generated at plant by rotating 3 coils in a magnetic field => power is sent out on 3 lines => power travels over wires to local area => power lines are connected to transformer => power is changed into specific voltage depending on which transformer is installed, and how the transformer is wired.
WYE or Delta configuration refers to how the 3-phase transformer coils are wired.
Inside each transformer are two coils: Primary coil is connected to power generation side. Secondary coil is connected to service wires that feed the service panel and circuit breakers.
If secondary coil is wound in WYE, then power to the service panel will always have a neutral, and two voltages.
Read
3-phase wiring
Larger image
277 480 Three Phase WYE

480 volts across line-to-line

277 volts line-to-neutral

Shows equipment ground
277 480 3-phase WYE
Use AG4803CE surge protector

Larger image
Three Phase 480V

480 volts across line-to-line

No system ground

Shows equipment ground
480 3 phase delta
Use AG4803D3 surge protector
Three Phase 480V delta corner ground

480 volts across line-to-line
3-phase wiring
Larger image
120 208V 3-phase wye

208 volts across line-to-line

120 volts line-to-neutral
3-phase wiring
Larger image
120 208V 3-phase wye
3 phase 4 wire
 
208 volts across line-to-line

120 volts line-to-neutral

Shows equipment ground
120 208 3-phase wye
Use AG2083C3 surge protector
120 208V 3-phase wye
Intermatic AG208C3 Surge
208 Volt 3-wire delta
3 Phase 3 wire 208 No Neutral

Phase to phase 208V
3-phase wiring
Larger image
347 600V three phase wye

600 volts across line-to-line

347 volts line-to-neutral
3-phase wiring
Larger image
347 600V three phase wye

600 volts across line-to-line

347 volts line-to-neutral

Shows equipment ground
347 600 3 phase wye
Use AG65033 surge protector
347 600V three phase wye
Intermatic AG65033 Surge Protection
How to wire 600 volt outlet
Larger image
Three Phase 600V

600 volts across line-to-line

No system ground

Shows equipment ground
How to wire 240 volt outlet and plug
Larger image
Three phase 250V

250V across each line

No ground
240 Delta 3-phase
Use AG2403D3 surge protector
High leg DeltaHigh leg delta  120-240 High leg Delta
Intermatic AG2403C3 surge protection

Black Line to Black Line 240V

Black Line to Neutral 120V

Red Line to Neutral 208V
120 240 high leg delta
Use AG2403C3 surge protector
240-480 High leg Delta

Phase to phase 480V

Phase A Phase C to Neutral 240V

Phase B high leg to Neutral 415V

Voltages are doubled compared with 120-240 high leg
High leg deltaImage shows Delta primary coil and High-leg delta secondary coil inside transformer
Read about transformers
Primary coil (or winding) is connected to power generation side.
Secondary coil is connected to service wires that feed the service panel and circuit breakers.

Configuration shows Delta primary coil. And High leg delta secondary coil.

If secondary coil inside transformer is wound in Delta configuration, there is no point where equal potential can be made between line and neutral.
The midpoint winding S3 is tapped which gives 120V or 208 volt to line.
S1 and S2 cannot carry any 120Volt loads.
As a result, the S3 coil is used for all 120Volt loads, plus 1/3 all 3-phase loads, causing potential imbalance.
120Volt loads must not exceed 5% Kva

Read
How to wire 480 volt outlet and plug
Larger image
277 480 Volts Single phase

With equipment ground
277 480 single phase
Use AG48013 Surge protector
277 480 Volts Single phase
Intermatic AG48013 Surge
Household wiring
120volt single-phase and 240 Volt split-phase

Intermatic IG1240RC3
Whole house surge
Larger image
Intermatic IG1240RC3 whole house surge protector/ pdf
Protect your business/ Protect circuit breaker panel and 120V and 240V circuits/ protect your tankless water heater, and any water heater with electronics
Installed directly into circuit breaker panel/ Replaced after each event
Protects circuit breakers, main panel, electric wiring, electronics, appliances
Does not protect TVs connected to sattellite dish/ for TVs use surge protector with co-ax TV connector
120 240 single phase120 volt single phase
UUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUUU
Additional links:

 EJ500 Utilitec Tork ST01C  ST01C UPM Aube T1032Aube Intermatic EI500Intermatic
    Water heater
GE  Leviton Hagar Gardena T1030  Gardena
Brinks timer Brinks
Westek TE06WHB Woods  Power pack
Timex
 Countdown
Westinghouse timers
Westinghouse
Sylvania

Omron
 Dayton Westek timers
Westek
Woods 49028
Outdoor timers

Power strips
3-phase timer
3-phase timer
Diehl timers
Diehl timers

Intermatic parts
Intermatic trippers and parts
How to wire Intermatic GM40
Intermatic GM series
How to wire Tork DTU40
Tork-DTU40
Sylvania timers
Tork timers and manuals
Tork TU universal timer
Paragon timers and manuals
Tork TU universal timer
Westek box timers

How to set analog  timers
Westinghouse timers
Westinghouse timers
Timex timers
Brinks timers
Gardena timers
Gardena T1030

Wire GE 15207 timer

GE box timers

Intermatic EH10 timer
EH10 timer
Intermatic T1906 and T1905
  
Intermatic T-101 T103 T104
Intermatic EH40 and WH40
  
Troubleshoot intermatic
Intermatic sprinkler timers
Intermatic pool timers and manuals
Intermatic T104P201
Intermatic timers
Intermatic GM series
Intermatic GM series
How to wire Intermatic GM40

E-mail: info@waterheatertimer.org
Site map