How to wire single water heater timers

Back to: Step 1: Gather Materials

Back to: Step 2: Connect wires
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI

Larger image
Neutral required:
This plan draws hot and neutral from any outlet box.
Applies to all programmable timers, countdown, wifi and zwave home automation devices.

Buy:
Programmable timer
Countdown timer
Zwave switch
Wifi switch
z-wave switch
Larger image
Neutral required:
This plan draws hot and neutral from any outlet box.
Applies to zwave home automation devices.

Buy:
Zwave switch
ST01C timer controls 240Volt water heater
Larger image

No neutral required:
Intermatic ST01C is best choice/ no neutral required
7-day programmable timer/ or dawn-dusk or dusk-dawn
Timer rated max 15 amp AC voltage: Use Fuse and fusholder
        
Buy:
3-way switches at Amazon
Intermatic ST01 timer at Amazon

Resource:
More wiring for ST01C + ST01C programming
Intermatic timers: ST01C & Ei600
Materials list/ and step-by-step for timer project
1003px
Busman fuseholder
Buy fuseholder that accepts terminals

Solder can melt with the flow of amperage

Solder can only be used for structural wiring such as intercom, phone, doorbell etc
Buy: fuseholder:
Buy fuseholders
ANL fuseholder
Buy:
Terminal kit at Amazon with crimp tool
Electrical terminals at Amazon
Blue 14-16 gauge female terminals 20 pcs at Amazon
Yellow 12-10 gauge female terminal 16 pcs
360 pc assortment at Amazon
ST01 timer More uses for ST01 timer

ST01 timer controls water heater or any 240 volt load
Resource: Control motor with ST01 timer

Reverse ST01 using Intermatic air switch   /
Resource
: Intermatic air switches

Use ST01C for 4-way timer

ST01 24 volt DC photoeye

Convert single-pole switch into 3-way switch using ST01/
 Resource: How to add a switch   How to add 3-way switch

ST01 timer controls HVAC
FD water heater timer FD and FF spring-wound countdown timers 
Timer powered by mechanical spring instead of voltage
Connect either terminal to either wire

Buy:/ compare all brands countdown timer:
Countdown timers
contactor
Larger image
2-pole 40 amp contactor
With removable dust cover on top.
Select correct voltage needed to control coil.
Water heaters typically use 240 volt coil, HVAC replacement is 24 volt coil. Typical 2-pole contactors are rated with 24, 120, 208-240 volt coils. Three pole contactors for 3-phase are available in more coil voltages not found in residential applications such as 277, 480 etc. Using the wrong coil voltage will cause problems. Selecting a contactor rated for more amps is better, so using 240 volt 40 amp contactor for 240 volt 30 amp water heater is fine.

Buy 2-Pole 40A resistive
120Volt coil
40 amp 240Volt coil
24 volt coil
Packard contactor
Mars 2-pole and 3-pole contactors
Rheem HVAC replacement contactors
50 amp contactor
60 amp contactor
45EG20AF in box
Larger image
2-pole 40 amp contactor in 6x6x4 enclosure
Using #8-32 x 3/4" bolts
Install contactor at angle leaves room for wire

Contactors are DPST
Double pole, single throw.
Both wires in 240 volt circuit can be switched on-off at same time

Buy:
Indoor 6x6x4 metal pull box with cover and knock-outs
Indoor 6x6x4 pull box with knockouts on 4 sides/ Wiegman
Outdoor 6x6x4 box with bottom knockouts

Indoor 6x6x4 metal pull box with cover and knock-outs/ Raco
Indoor/ hinged door 10x10 x 6 / Bud Industries
Indoor / hinged door/ 6x8x4 box / Bud Industries

Bud industries boxes at Amazon
Arlington boxes at Amazon

Resources:

Contactors
How to wire contactor for water heater
Types of enclosures
Compare types of enclosures
How to identify Black hot wire inside box:
Requires ordinary tester. With residential 120 Volt wiring, each box has only 1 hot wire. By code the hot wire is black. This test assumes you are testing ceiling box,  wall box with plug, wall box with multiple plugs, outdoor box, wall box with several switches, wall box with one switch. Test does not necessarily work with 3-way switch, since switch on other end can affect outcome. Test does not work with 240V circuits.
Turn off power. Mark wires with tape and numbers. Take photo of wires. Disconnect all wires from each other and separate. Turn power back on. Using ordinary tester, test each wire to bare ground. Only one wire will show power when tested to ground. That is the Black hot wire. Mark it. Turn off power. Reconnect wires.

Resources:
See basic water heater circuit
Figure Volts Amps Watts for water heater
Keep wires straight
Use solid copper wire
If wiring terminal or end of wire are covered with green, use emery board to clean terminal and sandpaper to clean wire.
Insdulation under screw plate
Larger image
Both wires MUST be same gauge
Straighten each wire
If wire is corroded or overheated, clean the end with sandpaper and wipe with cloth.
If wire has been melted, cut back and reattach, or replace wire.
Tighten screw very tight against copper wire

Use wire connector  
Push on wire connectors
Use push-on wire connectors
3 wires/ or different gauge wires
Join wires with wire connector or push-on connector
Run jumper to screw terminal.
Buy:
Push on wire connectors at Amazon
Red 3P connector (shown) for 10-14 gauge wire
Connector assortment
Resource:
How to select and install wire connector
Fire safety/ Do not put stranded wire under screw plate
Do not install stranded wire under screw.
Problem1: picture shows 2 different gauge wires under screw plate
Problem2: Stranded wire will expand and contract and come loose under screw plate, even if it is the only wire under the screw plate
Attach stranded wire and solid wire with wire connector, and run solid copper jumper wire to screw terminal
Take photo of wires before starting.

Resources:
Timer caught fire
Load ratings for Intermatic timers/ pdf


Larger image
10-3-wire
10-3-wire  12 Ga
10 gauge or 12 gauge?
Compare your wire with short pieces of 10 and 12 gauge wire from local box store

10 gauge for 30 amp breaker.
10 gauge wire can have black-white and sometimes black-red

12 gauge for 20 amp breaker
12 gauge will have black and white wires
.
Resources:
Match color code and amp rating for wire
Basic house wiring
Add black tape when White wire carries voltage (applies to 208 and 240V circuits)
With 120 and 277 Volt circuits, White wire is Neutral, and Black is Hot
With 208 and 240 circuits, both wires are Hot, and both wires carry voltage
Black tape on White wire identifies wire is Hot and not Neutral
Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Install and troubleshoot garbage disposal Waste King disposal
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks: