Recirculation off delay timer
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI
Skylink remote control countdown timer
Skylink wireless countdown

Skylink wireless countdown
Estimate 1/3 Hp
120V 60 Hz/ 10 watt minimum/ 1500 watt
Operate as ON-OFF or Countdown device/ Up to 500 feet
15 minute - 60 minute countdown

Buy:
Wireless wall mount transmitter TB-318 at Amazon
Wireless countdown receiver PA-318 at Amazon
Transmitter and receiver
Resource:
PA-318 manual
Control recirculation pump using One Shot timer
twin timer Choose Twin (cycle) timer or One shot timer mode
Input voltage from 100-240 volt. Some models, 12-24 volt AC-DC input.
Choose mode between One shot or Repeat-cycle.
Timer has dry NO NC terminals, so you can connect any voltage to switch terminals.
Set Repeat cycle or One shot Mode
To set One Shot (also called: on delay, off delay, or countdown ... where a load turns on for set period of time and then turns off until timer is reset) - Apply power to timer. Press MD for 3 seconds. Press MD to choose settings: minute, second, hour. When t,nod appears, select the 4 dashes, then press and hold MD button for 3 seconds to exit Mode. To set times, the Lock mode must be OFF.
Once you exit Mode, press RES button to set time A and then press MD to set Time B.

One shot mode is either On delay or Off delay depending how timer is wired. After the time period expires, the load turns OFF or ON and remains ON or OFF until you reset by momentarily connecting and then disconnecting terminals 4 and 3 with a Normally open push button (like a doorbell button), or timer, home automation, momentary switch etc... or reset timer by disconnecting and reconnecting power to timer.

To set Repeat cycle (this is for a blinking application on-off-on- ... or a repeating either-or application like christmas display blinking red-green-red-green etc until power is disconnected) - Apply power to timer. Press MD for 3 seconds. Press MD to chose settings: minute, second, hour. When t,nod appears, select the rectangle with dashes, then press and hold MD button for 3 seconds to exit Mode. To set times, the Lock mode must be OFF.
Once you exit Mode, press RES button to set time A and then press MD to set Time B.
If seconds are chosen for time period A, then time period B must also be seconds.
For example a car alarm is a cycle or twin timer ... honk-honk-honk indefinitely until power is cut.
Christmas displays, and blinking store lights etc use twin timer in repeat cycle mode.

Timer starts when it receives power and stops when power is off. Then it restarts when power resumes.
For example you can set the repeat cycle to turn on for 10 minutes and off for 99 minutes. Mode A would be 10 minutes, Mode B would be 99 minutes.
Or ... turn on for 10 minutes and then turn on another circuit for 99 minutes.
recirculation off delay timer
Larger image


recirculation off delay timerLarger image
Load
Max rated load on the timer is 10 amp.
Using a relay will preserve life of timer since motor start-up pulls surge of amps through terminals 8-7 on the one-shot timer.
How it works:
Set twin timer to one shot mode ... instructions shown in section above.

Connect 120 or 240 volt AC power to terminals 10-9. Connect other wires as shown.
Off delay uses terminals 8-7 as shown (or 11-12) ... while on delay would use 7-6.

Push doorbell button, or momentary toggle switch ... this will start the inkbird one-shot timer timer (do not energize the doorbell wires on start switch circuit with any voltage).

Timer turns ON and begins countdown. Timer terminals 7 and 8 turn ON. This causes the pump to turn on ... or causes the relay or contactor coil to energize. Circuit to recirculation pump turns ON.

When countdown expires, terminals 7 and 8 turn OFF, pump turns off, or relay coil or contactor coil is de-energized and pump turns OFF.
Twin timer that is set to one-shot mode, and powered by 120-240V, will operate .9 seconds to 99 hours. So the pump can run any length of time: for example 1 hour or 21 minites etc.
Do not connect power to terminals 1 thru 5.
How to wire twin timer

Buy: Project materials:
Twin timers at Amazon
Sestos twin timer
Omron DH48S twin timer
Normally open Push button
Example 50' thermostat wire

Buy
1EJG9 relay at Amazon
power relay 24v coil
30 amp enclosed power relay
25 amp Omron enclosed power relay

More off delay and pin timer illustrations
off-delay timer for recirculation system
Larger image
Always use contactor (or relay) to energize heavy amp load
Why?
So high amperage (and heat) does not flow through the timer ... instead the only amperage flowing through the relay located at terminals 8-7 will be to energize the 27 watt coil on contactor.
Using a contactor will extend life of timer, and protect overall integrity of circuit.

Suggest using a line fuse for power going to 9, and then jumper a wire from 9 to 8. This will ensure timer cannot be exposed to high amperage

Buy:
Twin timers at Amazon
Sestos twin timer
Omron DH48S twin timer
Contactor with 120Volt coil
Advantage of this one-shot timer: the reset does not require power to be turned off then back on, wires going to remote locations carry no voltage, and you can have 2-3-4-5 etc remote locations.
Other advantages: hardwire is cheaper, more reliable and long lasting than home automation, and the design is modular for easy part replacement.
Push button
Momentary contact switch

This is best choice since it can fit into electric switch box that is mounted in wall.
Resource: How to install old work box
Terminals 3-4 on the twin timer are for Reset.
When terminals 3 and 4 are momentarily touched together using a momentary switch or a push button, it starts the recirculation pump.
When the programmed time expires, the recirculation pump turns off, and the timer waits until the Reset is activated again.

Do not apply power to terminals 3-4. For the reset to work, terminals 3 and 4 need to be joined or touched together and then disconnected from each other.
If an ordinary on-off toggle switch is used instead of a momentary switch, the the toggle must be turned on and then off for the Reset to take place.

Buy:
Leviton momentary contact switch
Momentary contact switches
Push button                    Busman fuse holder
Buy from my affiliate links
Normally open push buttons
Normally open or monetary on push button
Fuseholders at Amazon
ST01C timer controls 120Volt delay-off-timer
Activate off-delay timer using push button -or- using ST10 timer
Push button, or ST01, activates delay timer.
Push button gives momentary on-off to activate delay timer
When ST01 turns ON and then OFF, then delay timer activates
Delay timer turns Load ON
Delay timer begins countdown.
When countdown expires, delay timer turns Load Off
How to wire AH3 delay timer

Buy:
6A855 Solid State timer at Amazon
11-pin plug-in base at Amazon
Contactor with 120volt coil
ST01 battery-operated timer
Resources:
6A855 Manual
More off-delay timers
remote control countdown timer
Larger image
Remote control countdown timer
Buy:
AH3 timer
11-pin plug-in base at Amazon
General purpose relay
Woods 32555 at Amazon
GE at Amazon
Wireless remote controls at Amazon
Replacement A23 battery at Amazon

Resources:
Select recirculation pump
See analog plug-in timers
See remote controls
Water heater recirculation system
WeMo switch WeMo Module
Control water heater with WeMo
Buy from my associate links:
WeMo switch
WeMo at Amazon
Belkin WeMo at Amazon


6x6x4 box

6x6x4 Box with cover
Metal box comes with knock-outs
Plastic box/ drill 3/4" for 1/2' knock out
Buy from my associate links
6x6x4 metal enclosure
6x6x4 PVC plastic enclosure\
Step drill bit for drilling into PVC box
contactor
Contactors
2-Pole 40A resistive
Rated 1 million operations
Inrush 27 watts, 7 watt operation
Buy from my associate links
120Volt coil At Amazon
240Volt coil At Amazon

Other contactors
Mars 2-pole and 3-pole
3-pole contactors
Resources:
Read more about contactors
Wire less transmitter TC-318 Skylink
At Amazon
3-button remote control transmitter TC-318-3
At Amazon
Wireless wall mount transmitter TB-318
At Amazon
Wireless on-off receiver MR-318 hardwire 300 watt
At Amazon
Wireless on-off receiver MR-318 plug-in 1500 watt
At Amazon
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker.

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
    
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Armored cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

Non metallic flexible cables must carry ground wire, but does not have hazard of short circuit causing injury from shock.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Armored cable
Southwire armored cable cutter
Non-metallic flexible conduit
Power whip
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but issues of insulation failure, lack of proper grounding, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems pose a risk to anyone working on electric power.

Buy:
Electrician tools kits
Klein tools
Tools kits
stranded wire
12 ga Stranded wire is good for conduit with multiple wires ... but stranded cannot be installed under screw terminals on outlets, switches, timers etc without risk ... of heat causing splayed strands ....that come loose ... and begin to arc. Connect stranded to short piece of solid copper wire, and attach solid to screw terminal. Do not solder residential or commercial wiring.
Buy:
Rolls of stranded wire

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistances and heat on wire and creates possible weak point.
Buy tools:
Wire strippers at Amazon
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line
Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Install and troubleshoot garbage disposal Waste King disposal
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook