How to wire Intermatic PF1112 freeze control
How to wire PF1202T
How to wire PF1222TB1
How to wire control center
PF1112T T104 with freeze thermostat
PF1112T
Larger image

PF1112T/ freeze control / plus one T104M 240Volt mechanism/ 3 Hp/ 40 amp timer
Knock outs for GFCI outlet/ or switches
Buy control center:
PF1112T panel/  no breaker slots, 1 timer at Amazon

Resources
Sell sheet with dimensions/ pdf
Sell sheet with models
Parts sheet /pdf
PF1112 manual
Wiring illustration for PF1112T freeze control and T104 timer
Buy parts
Freeze replacement at Amazon
PF1102M 240Volt freeze replacement with relay
Add fireman switch to timer/ from Amazon
Trippers156T1948A set at Amazon (dial hold up to 12 on and 12 off trippers)
Replace clock motor: WG1573 208-277V Amazon
Buy T104M clock mechanism at Amazon
Buy T104M201 clock mechanism with fireman switch at Amazon
PF1112T wiring
Large image of wiring

The PF1112T has one T104 240 volt timer, plus freeze control thermostat, and relay.
The relay is necessary to handle 40 amp capacity same as T104 timer. The thermostat can be purchased separately to replace one that is no longer functioning. Thermostat is not rated for 40 amps. Buy Intermatic replacement thermosat

The thermostat is mechanical bi-metal switch that reads approximate temperatures. Thermostat activates when temperature falls below set point. This activates the relay. The relay closes (turns ON) two circuits that override timer. If the timer is ON, the 240 volt pump will stay ON. If the timer is OFF, the pumps will turn ON and stay on until temperature rises above thermostat set point.

240 volt enters control panel with 2 Hot wires.  Hot wire 1 connects to terminal 1 and a jumper wire runs from terminal 1 on timer to contact 1 on relay. A wire runs from contact 1 on relay to the freeze thermostat.
Hot wire 2 connects to terminal 3 and a jumper wire runs from terminal 3 on timer to contact 3 on relay. A wire runs from contact 3 to the relay coil. Another wire runs from the other side of the relay coil to thermostat.
The pump connects to terminal 2 and terminal 4 on the T104 timer. A jumper wire runs from terminal 2 to contact 2 on relay. A jumper wire runs from terminal 4 to contact 4 on relay.
PF1202T freeze control
PF1202T
Larger image
PF1202T/ freeze control / plus two T104M 240Volt mechanism/ 3 Hp/ 2-40 amp timers
Knock outs for GFCI outlet/ or switches
Buy control center:

PF1202 freeze control panel / no breaker slots/ plus 2 timers  At Amazon
Buy parts
PA102 thermostat and relay
Freeze thermostat replacement at Amazon
Freeze control relay 143T135 at Amazon
Add fireman switch from Amazon
Trippers156T1948A set at Amazon (dial hold up to 12 on and 12 off trippers)
Replace clock motor: WG1573 208-277V Amazon
Buy T104M clock mechanism at Amazon
Buy T104M201 clock mechanism with fireman switch at Amazon

Resources
Sell sheet with dimensions/ pdf
Sell sheet with models
Parts sheet /pdf
Parts sheet 2
PF1202 manual
PF1202T manual
Intermatic pool parts catalog/ pdf
PF1202T freeze control
PF1202T
Larger image
PF1202T/ freeze control / plus two T104M 240Volt mechanism/ 3 Hp/ 2-40 amp timers
Knock outs for GFCI outlet/ or switches
Buy control center:

PF1202 freeze control panel / no breaker slots/ plus 2 timers  At Amazon
Buy parts
PA102 thermostat and relay
Freeze thermostat replacement at Amazon
Freeze control relay 143T135 at Amazon
Add fireman switch from Amazon
Trippers156T1948A set at Amazon (dial hold up to 12 on and 12 off trippers)
Replace clock motor: WG1573 208-277V Amazon
Buy T104M clock mechanism at Amazon
Buy T104M201 clock mechanism with fireman switch at Amazon

Resources
Sell sheet with dimensions/ pdf
Sell sheet with models
Parts sheet /pdf
Parts sheet 2
PF1202 manual
PF1202T manual
Intermatic pool parts catalog/ pdf

How to wire freeze thermostat
PF1202T wiring

PF1222TB wiring
How to wire PF1202T and PF1222TB

Your incoming 240 volt connects to terminals 1 and 3 on FILTER timer....
Clock motors for both timers MUST connect to live 240 volt. This means clock motor on CLEANER timer must connect to terminals 1 and 3 on FILTER timer, or to a team block where 240 volt arrives inside the control center. This wiring ensures that both clock motors are running at all times, and both yellow dials are rotating once per day.

On a control center WITHOUT freeze override, terminals 1 and 3 on CLEANER timer connect to terminals 2 and 4 on FILTER timer .... this means CLEANER can only turn ON when FILTER pump is ON...

On a control center WITH freeze override, terminals 1 and 3 on CLEANER timer connect to the freeze control as illustrated, and then connected to terminals 2 and 4 on FILTER timer .... this means CLEANER can only turn ON when FILTER pump is ON, same as control center without freeze.

The freeze override will send power to the Cleaner timer when temperatures drop below thermostat set point
T104 and freeze control
Larger image
How to wire PF1120
T104 timer connected to PF1102 
Freeze thermostat and relay
Freeze control by-pass timer and turns pump On when temperature drops below freezing.
Resources:
How to wire T104
178T24 freeze thermostat  Intermatic freeze control PA102 178T24 stand-alone 15 amp Thermostat
PA102 thermostat and 40 amp relay
Buy
PA102 mechanical thermostat and SPDT relay
178T24 Amazon
Freeze thermostat

Resources
178T24 wiring
How to wire
Freeze control thermostat Override switch with 178T24 freeze control
Up to 30 amp
Freeze control override switch

Buy:
Leviton 3032 30 amp switch at Amazon
Leviton 30 amp switch at Amazon
30 amp switches at Amazon<
Keep wires straight
Use solid copper wire
If wiring terminal or end of wire are covered with green, use emery board to clean terminal and sandpaper to clean wire.
Insdulation under screw plate
Larger image
Both wires MUST be same gauge
Straighten each wire
If wire is corroded or overheated, clean the end with sandpaper and wipe with cloth.
If wire has been melted, cut back and reattach, or replace wire.
Tighten screw very tight against copper wire

Use wire connector  
Push on wire connectors
Use push-on wire connectors
3 wires/ or different gauge wires
Join wires with wire connector or push-on connector
Run jumper to screw terminal.
Buy:
Push on wire connectors at Amazon
Red 3P connector (shown) for 10-14 gauge wire
Connector assortment
Resource:
How to select and install wire connector
Fire safety/ Do not put stranded wire under screw plate
Do not install stranded wire under screw.
Problem1: picture shows 2 different gauge wires under screw plate
Problem2: Stranded wire will expand and contract and come loose under screw plate, even if it is the only wire under the screw plate
Attach stranded wire and solid wire with wire connector, and run solid copper jumper wire to screw terminal
Take photo of wires before starting.

Resources:
Timer caught fire
Load ratings for Intermatic timers/ pdf


Larger image
10-3-wire
10-3-wire  12 Ga
10 gauge or 12 gauge?
Compare your wire with short pieces of 10 and 12 gauge wire from local box store

10 gauge for 30 amp breaker.
10 gauge wire can have black-white and sometimes black-red

12 gauge for 20 amp breaker
12 gauge will have black and white wires
.
Resources:
Match color code and amp rating for wire
Basic house wiring
Add black tape when White wire carries voltage (applies to 208 and 240V circuits)
With 120 and 277 Volt circuits, White wire is Neutral, and Black is Hot
With 208 and 240 circuits, both wires are Hot, and both wires carry voltage
Black tape on White wire identifies wire is Hot and not Neutral
Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Install and troubleshoot garbage disposal Waste King disposal
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook