How to wire photoeye so it turns off 4 hours later
1-2-3-4-5-6-8 hours later
Down to the minute, second, or hours
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI
Add delay timer to photoeye circuit
Light turns on normally at dusk, then turns off after preset time expires.
Set the delay timer to the exact minute, second or hour.
Delay timer activates when photeye turns ON, and light turns on normally.
When delay period expires, the light turns off, and timer resets to zero,. Timer and light remain OFF until photoeye activates the circuit again next night.twin timer

Buy:
Twin timers at Amazon
Sestos twin timer
Omron DH48S twin timer
Resource:
Twin timer manual
Omron twin timer manual
Twin timerChoose One shot mode
Input voltage from 100-240 volt. Some models, 12-24 volt AC-DC input.
Choose mode between One shot or Repeat-cycle.
Timer has dry NO NC terminals, so you can connect any voltage to switch terminals.
Repeat cycle or One shot Mode
To set One Shot (also called: on delay, off delay, or countdown) - Apply power to timer. Press MD for 3 seconds. Press MD to choose settings: minute, second, hour. When t,nod appears, select the 4 dashes, then press and hold MD button for 3 seconds to exit Mode. Once you exit Mode, press RES button to set Time A and Time B. To set times, the Lock mode must be OFF.
Once you exit Mode, press RES button to set time A and then press MD to set Time B.
If seconds are chosen for time period A, then time period B must also be seconds.

One shot mode is either On delay or Off delay depending how timer is wired. After the time period expires, the load turns OFF or ON and remains ON or OFF until you reset by momentarily connecting and then disconnecting terminals 4 and 3 with a Normally open push button, or timer, home automation, etc... or reset timer by disconnecting and reconnecting power to timer.

You can pause the timer by connecting terminals 2 and 4, or reset timer by momentarily connecting terminals 4 and 3.
You can control power to the twin timer using a 7-day timer for example, or another twin timer, home automation device etc.
Buy:
Twin timers at Amazon
Sestos twin timer
Omron DH48S twin timer
Resource:
Twin timer manual
Omron twin timer manual
Resource:
How to wire twin and one-shot timers
Add 60 minute delay timer to photoeye circuit
Max on-off timer is 60 minutes for AH3
Light turns on normally at dusk, then turns off after preset time expires.
Set the analog delay timer to the approximate minute, second or hour.
Delay timer activates when photeye turns ON, and light turns on normally.
When delay period expires, the light turns off, and timer resets to zero,. Timer and light remain OFF until photoeye activates the circuit again next night.

Illustration shows AH3 delay timer. Also pictured below.
AH3 off delay timerBuy from my affiliate links
AH3 timers at Amazon
st3pf relay

Resources:
Use off-delay to control recirculation pump
Use off delay to control motors
AH3 off delay timer
Timer coil voltage 120V AC.
Contacts rated 3 amp at 240 Volt -or- 6 amp at 120 Volt
Volts x amps = watts/ 6 amp x 120 volt =  720 watts
Max 1/4 HP: bath fans are usually 1/6 Hp or 1/3 Hp. Recirculation pumps 1/25 Hp.
1/3 Hp attic fans are probably to large amp draw for this timer to operate long-term.
For long term, keep load amp draw smaller than load rating... or connect timer to contactor
AH3-3 timer
Can be used as relay, ON-delay, OFF delay, or all 3 at same time.
0-60 minute settings are approximate... experiment to fine tune setting.
8-pin base included with 8 screw terminals. Remove timer from base to attach wires.
Recommend tightening screw plates very tight against wire, especially if using stranded wire.
Stranded wire can become solid wire by adding solder.
Solid wire is not fire hazard. Stranded wire is greater fire hazard when under screw plate.
Size: 2-1/2" tall with base included  x 1-5/8" x 2"
120 volt off delay timer/ Contacts rate 120-208-240 Volt
Rated for all loads incandescent (Tungsten), LED, CFL, resistive, inductive etc
Rated 3 amp @ 240 volt -or- 6 amp @ 120 volt/ Up to 1/4 Hp @ 120 Volt
120 volts x 6 amps = 720 watt.
Bath fans are OK at 1/6 Hp/ Attic fans can run 1/3 to 1/2 Hp... suggest use contactor to carry load
Recirculation pumps are 1/25 Hp and delay timer works fine.
Buy from my affiliate links
AH3 timers at Amazon

Resources:
Use off-delay to control recirculation pump
Use off delay to control motors
Fuseholders
Omron H3CR sell sheet and wiring
DH48S one-shot timer 8 pin timer wiringDH48S twin timer used as one-shot
It is possible to use this timer for one-shot (off-delay) application IF...
Let's say you want a one-shot timer that turns ON a light while a machine is operating, and then light remains ON for 55 minutes afterwards before turning OFF.
You select Minutes (M) for time A, and set time for 55.
Then select Hours (H) for time B, and set for 99 hours. Then as long as the machine-and-light circuit turned ON again before the 99 Hours expires, the timer will function as a one-shot.

Another example: You want outdoor light to turn ON normally at dusk using a dusk-dawn photoeye, but then light turns OFF 4 hours later.
Select Hours (H) for time A, and set time for 4.
Select Hours (H) for time A, and set time for 4.
Then select Hours (H) for time B, and set for 99 hours. Since the outdoor light turns ON again before the 99 hour expires, the DH48S will function as one-shot timer.
Buy
Uxcell DH48S-S twin time
Resource:
How to wire photoeye so it turns off after 4 hours
Add several layers of control using twin timer, delay timer and 24-hour or 7-day timer
Image show test wiring

Buy
Din rails
THc15 timer
AH3 delay timer
Indicator lights
How to wire H3CR timer

Resources:
How to wire delay timer
How to wire din rail timers + manuals
Busman HKP-HH fuse holder


Busman fuse holder/ panel mount/ drill 1/2" hole
Some fuseholders accept terminal connections, some have solder-only 15 Amp ceramic fuseconnections. 
Fuse blocks have screw terminals.

Buy:

Panel mount fuse holders at Amazon
ANL fuseholder

Buy: fast and slow acting fuses:
Ceramic fuses at Amazon
Fast acting ceramic fuses
Din Rail fuse holder/ din rail mount/
Din rail is surface mount

Buy:
Din Rail fuse holder

Buy:
2T511GA Nema3R enclosure at Amazon
10 amp Relays
10 amp LY2 relays
LY3 relay
120 volt LY2
15 amp Din rail timer
Din rail Fuseholder
Resources:
Din rail timers
Off Delay timers
On delay timers
Build 3-phase astronomic timer
Build 2-speed timer for pump, motor etc

How to wire contactors/ relays
Busman HKP-HH fuse holder
How to wire inline fuseholder
AH3 off delay timer
How to wire delay timers
How to wire twin timers
Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Install and troubleshoot garbage disposal Waste King disposal
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook