How to wire Hayward 2 speed pump

T106 2-speed timer

T106R / 240 Volt / NO NC
Buy
T106R outdoor at Amazon
Resource
T106 series models/ manuals

T176 T176R
Buy
T176 indoor at Amazon
Resource
T106 series models/ manuals
T106P3
T106P3
Buy
T106P3 beige plastic box
T106R metal gray box at Amazon
Resources:
T106 manual
T10604R manual
T106 series models/ manuals
T106M
T106M/ mechanism
Buy
T106M at Amazon
Resource
T106 series models/ manuals
T106 2-speed pump
>2-speed pool pump wire colors may be different than illustration
>For example High speed might be White and Low speed Yellow
Connect Low speed to NC terminals. High to NO terminal.

T-106 timer: 2-speed 240Volt pump

>Timer acts as a high-low switch for continuous-running 2-speed pumps.
T106 timer does not turn pump off. Use P1353 for 2-speed pumps that turn off
>Or use 2 timers, and wire first timer before T106.

See wiring diagram for two timers

Wire colors will be different. For example white wire may be Low speed.
wiring diagram and instructions for pump
Typically Low speed is running most of the time
So connect Low speed wire to NC terminal 1, and High speed wire to NO terminal 4.
Set timer to turn ON during times when High speed is needed.
Minimum on-off is 1 hour.
>Pump operates continuously. Install another timer on L2 Hot line to turn pump ON-OFF
Pump motor must be grounded
Resources:
How to set Intermatic T100 series timers
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI
baseboard heater wiring
Larger image

Buy
T106M at Amazon
Hayward 2 speed pump
Hayward pumps at Amazon
Hayward pool equipment

Resources:
How to wire GFCI
For 240 volt 1 Hp motor, use 12-3 wire between control center and pump
Resources:
Match color code and amp rating for wire
How to wire subpanel
Figure Volts Amps Watts
T10604 control center for 2 speed pump
Uses T104 and T106 timers located side-by-side inside control center
No circuit breaker spaces

Buy
T104 mechanism
T106 mechanism
T10604R with T106 and T104  /208-240V for 2-speed pumps
Pentair pool
Hayward pool
Intermatic parts sheets
Resources:
Control centers and parts
Digital control centers and parts
Freeze control centers and parts
T10604R wiring
T10604R wiring for 2 speed pump

For controlling 2-speed pool pump with minimum cost and long-term reliability. Replacement parts are available and installed DIY with screwdriver.
240 volts supply voltage is connected to Terminals 1 and 2 on T104 timer on right side.
Both timers have a clock motor that rotates the yellow dial once per day. The dial can hold up to 12 sets of trippers. Typically, the swimming pool timer has 2 sets of trippers for 2 OFF and 2 ON each day. Both clock motors are connected to terminals 1 and 2 on the T104 timer.

The way it works: T104 timer controls the on-off function for the pump. When T104 turns on, power is sent to T106 timer. T106 timer has NO and NC terminals. One set of terminals or the other set of terminals is ON at all times. When power arrives from T104, the power is sent to either low or high speed on the pool pump. Trippers on the dial of the T106 timer control when the pump is high speed or low speed. When power arrives at the filter pump from T106, the circuit is completed through terminal 4 on T104.

Build your own 2 speed controller

Any Hp motor or pump

40 amp relay & contactor = 5 Hp @ 240 volt


Buy from my affiliate links:
Buy 40 amp contactor with 120 volt coil
40 Amp DPDT relay at Amazon
Magnecraft 50-1289-1 relay box and cover

Resources:
How to assemble parts
Compare programmable timers
Wire size and amp charts for motors
Information on contactors
how to bond control panel
Example shows solar panels... but also includes pool control centers etc
Pump must be bonded to ground wire and then directly to ground rod... in addition to regular ground wire coming from electric service

Ground all electrical devices, and all household grounds together and bond to main breaker panel and to ground rod. Do not ground to water pipe:  Make sure ground is connected to ground rod.
Water heaters and metal water pipes will corrode with stray current.

Modern pex water lines are not affected, and cannot be used as a ground.

When installing new water heater, water pipe, doing repairs on plumbing, installing new electric service etc... check that all electric is connected to dedicated ground wire that is bonded to ground wire that is connected to outdoor ground rod.

Bonded means steel electric panel enclosure must be directly connected to ground wire that is connected to local ground rod.
Applies to outdoor control panel and pool pump at point of installation/ local codes vary / consult local electrician/ some codes may allow bonding to metal conduit that enters the soil at point of installation... but stray current corrosion can cause deterioration of this conduit/ codes vary for grounding for many reasons, such as different soils offer different resistivity to grounding/ for example dense wet soils conduct to ground better than loose dry rocky soils

Buy:
Ground rod and clamps at Amazon
Bonding lugs

Resources:
Why ground is important
Basic household wiring
See inside main breaker box
What is 3-phase electric
How to wire T100 series timers
How to wire Control centers
Bond motor to ground

Larger image

Horsepower / wire size / distance


Multimeter
Test for breaks in wire/ Test for voltage
Most appliance require 80% rated voltage to function correctly
Buy
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line
Resource:
How to test and replace element
How to test thermocouple
Element tests for 120 volts
How to test wire
Safety when testing wires:
Never touch wet or previously flooded appliance.
Never stand on wet surface when working on electric.
Never stand on bare soil, put down dry boards.
Tape tester leads to wood sticks to keep hands away from power.
Use non-contact voltage tester before touching wires.
Never touch or lean into any made of metal.
Remove metal objects from pockets.
Do not use oxygen or fuel accelerants in same room as electrical repairs

Resource:
Basic house wiring

Non-contact voltage tester
Test for power without touching connectors
NEVER assume power is OFF

Buy:
Non-contact voltage tester Amazon
Electric testers at Amazon
Resource:
How to test electric power is off
GFCI receptacle120 volt 15 amp devices including GFCI, timers, switches, plugs, wifi controls etc can be installed on 15 or 20 amp breaker.

120 volt GFCI, outlet, receptacle that is rated 20 amp can be installed on 20 amp breaker only, but NOT on 15 amp breaker.  
Buy
15 amp GFCI
20 amp GFCI
Buy
Basic electric book
Home plumbing/ electrical codes
Basic electric book
Or learn about basic household electricity... use and search my site/
Resource
Safe electric wiring
Basic house wiring

Use outlet tester to check for correct wiring on any 120 volt straight-blade outlet.
Buy:
Klein testers
Outlet tester
Circuit breaker finder
Electric usage monitor
wire connector assortment

Twist-on wire connector assortments

Do not reuse old connectors
Twist wire connector very tight. Pull wires to ensure they will not come loose. Cover all bare copper.
Buy:
Connector assortment at Amazon
Connector assortment at Amazon
Resource
How to select and install twist-on wire connectors
Weatherproof wire connector

Weatherproof wire connector

Connector cavity is full of silicone
Built-in cover keeps silicone in place
Protect from water, dust etc
Buy from my affiliate links
Weatherproof size 14 to 6 Amazon
Weatherproof size 22 to 8 Amazon

Resource
How to select and install connectors
Connect wire to screw terminal
Use only 600 volt solid copper wire.
Do not use stranded wire or extension cord.
Do not use solder anywhere on residential 120-240 volt wiring.
Attach electric installation to structure. Tighten screws very tight against wire.

Buy:
NEC books
Dewalt plumbing/ electrical codes
Basic electric book
National electric code guide/ illustrated

Resources:
How to twist wire
How to select and install twist-on wire connectors
Lever switchWeatherproof lever switch on outdoor lights
Safely operate outdoor toggle switch
Replaces outdoor cover
Install over top of ordinary switch
Works with single-pole, double-pole, 3PST, 3-way, 4-way switches etc
Use weatherproof box for outdoor
Can be used indoor or outdoor

Buy:
Best choice: Cantex lever switch
Outdoor lever switches at Amazon
Lever switches

Resource
Cantex-toggle-switch-covers.pdf
Cantex-PVC-junction-boxes.pdf

Treminals

Terminals

Buy:
Terminal kit
Blue for 16-14 wire
Yellow for 12-10 wire

Resource:
How to install terminal
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
remove cable staple
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

Code
-Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon

 
linesman pliers

When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistances on wire and creates weak point.
Buy tools:
Wire strippers at Amazon
Linesman pliers
Pro linesman plier
Needle nose pliers
End cutting nippers at Amazon

Weather resistant plastic box for outdoor extension cord connections, Christmas lights, outdoor power strip etc . Not for connecting wires with wire nutsŪ, or in-wall wiring, but can be used indoors to organize extension cords, power strips etc.
Weather resistant is not weatherproof or watertight. Use enclosures rated IP65 and IP67 for waterproof.
Extension cords cannot be used for permanent wiring.
Buy:
Large-medium-small electric cord box
Socketbox
Raintight enclosures
Water-tight cord lock
Resource: Enclosures and boxes

Use only solid copper wire, and no insulation under screw plate.

Tighten screw very tight against copper wire
Insdulation under screw plate
Larger image
Both wires MUST be same gauge
Straighten each wire

Max 2 wires under screw plate
Both wires same gauge

Larger image

Connect stranded and solid with wire nut and run jumper to screw plate.
Or add solder to stranded wire to make solid.
See example image

Use wire nut    
Push on wire connectors
Use push-on wire connectors

3 wires/ or different gauge wires

Join wires with wire nut or push-on connector
Run jumper to screw terminal.
Buy:
Push on wire connectors at Amazon
Red 3P connector (shown) for 10-14 gauge wire
Lever nuts for stranded wire at Amazon
Resource:
How to select and install wire connector

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook