Can I use Ground wire for Neutral?
Answer: No
Resource: Safe electric wiring
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
stranded wire
600 volt 12 ga Stranded wire ot THHN wire is good for conduit with multiple wires ... but stranded cannot be installed under screw terminals on outlets, switches, timers etc without risk ... of heat causing splayed strands ....that come loose ... and begin to arc. Connect stranded to short piece of solid copper wire, and attach solid to screw terminal. Do not solder residential or commercial wiring.

Project wire, extension cords, thermostat, bell and automotive wire are not rated for residential or commercial wiring. Only wire maked 600 volt can be used for permanent household wiring.
Buy:
Southwire 600 volt stranded wire
Rolls of stranded wire
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI

Stick menQuestion:
Can I use Ground wire for Neutral?

Answer: NO
The ground wire cannot be used as Neutral.
The Neutral and Ground are bonded (connected) together inside the main breaker box, so using a Ground wire as a Neutral works ... it will complete the circuit ... but it creates resistance (or impedance) that can interfere with correct and safe function of ground wire.
In event of short circuit, surge or nearby lightning strike, the overvoltage can push into any device that is improperly using the ground wire, creating a fire hazard.

The purpose of the ground wire is to create a continuous and resistance-free pathway for short circuits etc.
Adding the extra resistance caused by a Neutral load can impact the function of the circuit breaker, interfere with GFCI protection, increase human hazard, and add risk of fire.

The Neutral wire is bonded (connected) to the ground wire at service panel (breaker box). This mean the ground will work as a Neutral wire, but it is against Code and safe electric practice to do so.

If the Neutral wire at service panel becomes disconnected for some reason, then the 120 volt circuits, and any circuit that uses the Neutral wire to complete circuit, will feed power back through the ground wire and out to the ground rod. This means the electricity will reach all the metal enclosures and conduit in the home or building because the neutral and ground are bonded at the main panel (breaker box). The result is electrocution hazard.

Resource:
Why you need ground wire
How to find ground fault
How to find Neutral wire
What causes electrocution
Test for a grounded neutral
The best way to test for a grounded neutral is to use an ohm/continuity tester by turning the breaker to the off position and remove the load neutral from the breaker. Next, take one lead of your tester to the load neutral and the other lead to the neutral/ground bar in the panel. You should read no continuity. If you are getting continuity, go through entire circuit looking for the location where the bare ground is making contact to the neutral conductor. If you are using shared neutral homeruns, you must use a two pole arc fault breaker. You can not use single pole arc faults breakers with shared neutrals.

Combination GFCI
Combination GFCI
Switch & plug
Buy:
Leviton Combination GFCI
Combination GFCI  Amazon

Resources:
How to wire GFCI combo
GFCI receptacle
Leviton GFCI receptacle
Buy:
GFCI receptacle
Slim design for ez install
1.03 inch depth
GFCI receptacles Amazon
Decora wall-plates
Resources:
How to wire GFCI receptacle
GFCI nite lite
Leviton GFCI nite lite
Buy:
Leviton GFCI w nite lite
GFCI nite lights Amazon

Resources:
How to wire GFCI nite lite
GFCI nite lite
Leviton GFCI with LED lite
Buy:
Leviton GFCI w nite light
Slim design for ez install

Resources:
How to wire GFCI w/ LED
Leviton GFCI pilot light
Leviton GFCI pilot light
Buy:
Leviton GFCI pilot light
GFCI pilot lights Amazon
Pilot indicates power status
Resources:
How to wire GFCI pilot
main breaker box
Larger image

Question: Are both sides of 240 volt breaker 30 amp or 15 amp ?

Answer: both side of 240 volt breaker are 30 amp. You can make a 240 breaker by combining 2 single-pole breakers, but that code requires you to install a 'common bar' between the breaker so if one trips, then the other breaker also trips.
120Volt and 240Volt breakers
-Image shows 120Volt line and 240volt line.
-Both circuits have ground wire.
-Each 120 and 240 require two wires to complete circuit.
-120V requires 1 hot and 1 neutral
-240V requires 2 hots
-Ground wires are for safety.
Resources:
Read more about 240 volt

-Neutral not necessary to complete 240Volt circuit. However some 240Volt lines have additional neutral wire. However,
-240Volt lines can be white and black or red and black

-Modern breaker boxes have separate Neutral and Ground busbars that are bonded together electrically. Older boxes often have one busbar for both Neutral and Ground.
-Illustration shows Neutral and Ground busbars on same side of box so it is easier to illustrate wires. In actual box, the Neutral and Ground busbars are on opposite sides.
Resources:
Color code and wire sizes
Basic 120 volt and 240 volt water heater circuits
How to wire 240 volt outlets
How to wire 3-phase outlets and timers
How to convert 240Volt  water heater to 120volts

Multimeter
Test for breaks in wire/ Test for voltage
Most appliance require 80% rated voltage to function correctly
Buy
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line
Resource:
How to test and replace element
How to test thermocouple
Element tests for 120 volts
How to test wire

Safety when testing wires:
Never touch wet or previously flooded appliance.
Never stand on wet surface when working on electric.
Never stand on bare soil, put down dry boards.
Tape tester leads to wood sticks to keep hands away from power.
Use non-contact voltage tester before touching wires.
Never touch or lean into any made of metal.
Remove metal objects from pockets.
Do not use oxygen or fuel accelerants in same room as electrical repairs

Resource:
Basic house wiring

Non-contact voltage tester
Test for power without touching connectors
NEVER assume power is OFF

Buy:
Non-contact voltage tester Amazon
Electric testers at Amazon
Resource:
How to test electric power is off
GFCI receptacle120 volt 15 amp devices including GFCI, timers, switches, plugs, wifi controls etc can be installed on 15 or 20 amp breaker.

120 volt GFCI, outlet, receptacle that is rated 20 amp can be installed on 20 amp breaker only, but NOT on 15 amp breaker.  
Buy
15 amp GFCI
20 amp GFCI
Buy
Basic electric book
Home plumbing/ electrical codes
Basic electric book
Or learn about basic household electricity... use and search my site/
Resource
Safe electric wiring
Basic house wiring

Use outlet tester to check for correct wiring on any 120 volt straight-blade outlet.
Buy:
Klein testers
Outlet tester
Circuit breaker finder
Electric usage monitor
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX
Connect wire to screw terminal
Use only 600 volt solid copper wire.
Do not use stranded wire or extension cord.
Do not use solder anywhere on residential 120-240 volt wiring.
Attach electric installation to structure. Tighten screws very tight against wire.

Buy:
NEC books
Dewalt plumbing/ electrical codes
Basic electric book
National electric code guide/ illustrated

Resources:
How to twist wire
How to select and install twist-on wire connectors
Lever switchWeatherproof lever switch on outdoor lights
Safely operate outdoor toggle switch
Replaces outdoor cover
Install over top of ordinary switch
Works with single-pole, double-pole, 3PST, 3-way, 4-way switches etc
Use weatherproof box for outdoor
Can be used indoor or outdoor

Buy:
Best choice: Cantex lever switch
Outdoor lever switches at Amazon
Lever switches

Resource
Cantex-toggle-switch-covers.pdf
Cantex-PVC-junction-boxes.pdf

Terminals

Terminals

Buy:
Crimping tool kit
Blue for 16-14 wire
Yellow for 12-10 wire
Ratcheting Crimper

Resource:
How to install terminal
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon

Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

Code
-Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon

 


When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistances on wire and creates weak point.
Buy tools:
Wire strippers at Amazon
Linesman pliers
Pro linesman plier
Needle nose pliers
End cutting nippers at Amazon
6x6x4 pull box
6" Pull box
Junction boxes for conduit and wiring
Buy:
Bud industries 6x6x4 best value/ no KO
Raco 6x6x4 metal pull box
Wiegman 6x6x4 pull box
Hoffman 6x6x4 pull box
Adamax raintight enclosure
Raintight 6x6x4 box
Pull boxes
Buy:
Pull boxes
Polycarbonite boxes
Resource: Enclosures and boxes

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook