How to wire transfer switch

Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI
30 Amp Generator Transfer Switch Kit 30 amp Transfer switch
Safe maximum of 30 amp service is 24 amps.
The single breakers in this transfer switch are 15 amp, with 14 gauge wire... DO NOT use 15 amp for a 20 amp circuit in the main breaker panel, unless wires are changed to 12 gauge..
The double breaker in this transfer switch is 20 amp. Maximum wire size that is supplied with this transfer switch is 12 gauge ... both these are too small for residential water heater unless you a) replace transfer switch wire and breaker to 30 amp and 10 gauge or b) Replace water heater elements with 3500 watt and change main service panel breaker to 20 amp.


Why you need transfer switch

Purpose is to switch power OFF on specific breakers when you connect generator to household breaker panel..
When power goes out on the grid, any electricity that you generate can go backwards to the power company transformer and be converted to high voltage on the distribution wires. The existance of electricity of these wires is a danger to anyone coming into contact with the line, including linemen trying to do repairs. The situation slows repair and increase cost. As a result, a transfer switch is required to shut off home-generated power from reaching the main breaker panel and then out to the grid wires. Same requirement is true for home-generated solar power: it must be connected to equipment that automatically disconnects grid connection when grid power is OFF.

When you need transfer switch
Whenever you connect generator to any wire that is connected to main breaker panel.
You can run a generator and plug in tools etc without a transfer switch.
Buy
Transfer switch at Amazon

Resources:
Reliance 31406CRK manual/pdf
50 amp Transfer switch
Safe maximum of 50 amp service is 48 amps.

This product is supplied with a combination of 15- and 20-amp circuit breakers. Maximum two 30 amp double-pole breakers can be installed in the A and B positions.
To remove a circuit breaker, remove the circuit breaker compartment cover, unscrew the terminal screw in the breaker to be removed, removed the wire, tilt the top of the circuit breaker towards you and lift up and out.
Reverse the procedure to install another breaker. In addition, positions A and B (but only these positions) will accommodate 30-amp circuit breakers.

Buy
510 series 50 amp 10 circuit 12500 max 5 double breakers 1" conduit 12 gauge wires supplied
514 series 50 amp 10 circuit 12500 watt
Buy double-pole breaker:
Choose from 15 to 125 amp

Resources:
Reliance 510 manual/pdf
generator You can run a generator and plug in tools etc without a transfer switch as long as home-generated power is not connected to any household wiring
120 and 240 volt generators are used for homes and construction businesses etc
Check the total wattage output, portability vs need
If you are connecting the power to main breaker panel, you MUST turn off main breaker and disconnect from power company service ... or use a transfer switch.

Buy
Generators at Amazon

Resources
How to wire 240 volt outlets
SAFETY: Portable generators release more carbon monoxide—which is particularly dangerous because it is odorless and invisible—than most cars.... the fumes will get into house from garage
Symptoms: First symptom of CO carbon monoxide poisoning is lethargy and headaches that disappear when you leave the house. Prolonged exposure can kill whole family.
Call plumber immediately to check vent, clean burner and combustion chamber, check gas pressure, and      

What to do in event of CO poisioning
:
       1) Move affected people to fresh air.  Lay on side... not on back or they will suffocate
       2) Call for medical help.
       3) Open windows and doors.
       4) Call plumber to test and repair vents.
       5) Install CO detector.
       6) Maintain water heater once per year as shown in product manual
Buy:
Carbon monoxide detectors at Amazon
twist lock plug     
Twist-lock plug will not pull out of receptacle
Twist lock plug for extension cord that plugs into generator
Install 20 or 30 amp as needed.
X Y terminals go to either Hot wire.
W is always Neutral.
G is always ground.
These are standard markings for 240 volt plugs and outlets.
Connect X to one hot busbar inside the transfer switch, connect Y to other hot busbar, ground and Neutral to respective terminals
Buy:
Leviton 2711/ 125-250 volt/ 20-30 amp/ 3 pole
Resources
How to wire subpanel
How to wire 240 volt outlets, plugs, switches
Difference between single-phase and 3-phase
Image below shows main breaker panel without transfer switch
In a time of power outage, it is very important that generators are not sending power to the main panel, because that power will travel backwards out the main breaker and re-energize the distribution lines that enter house.
If the main distribution lines are still energized, that can be dangerous and slow the rate of repairs.
Image below shows Transfer switch installed
When generator is OFF, the transfer switch breaker is pushed one direction. Power leaves from the main breaker panel, travels through the transfer switch breaker, and then goes to 120-240V load.

When generator is ON, the transfer switch breaker is pushed the other direction. Power leaves the main panel breaker and travels to the transfer switch breaker .... but cannot go farther, so the transfer switch effectively turns off any power that could come from breaker, and turns off any chance of generator energizing the breaker panel and power company wires. When generator is ON power from the generator leaves the transfer switch breaker and travels to the load.
Each main panel breaker that is wired into the transfer switch will operate the same.
The transfer switch only designated loads that are connected as illustrated below.
Transfer switch
Image below shows how to toggle water heater from 240 volt to 120 volt
Works any time, not just when the generator is on.
If your transfer switch does not have 30 amp breaker it is a problem UNLESS you change elements to 3500 watt,  in which case water heater will work fine with 20 amp.
The math: Volts x amps = watts.
4500 watt element divided by 240 volt = 18.75 amp
So technically a 20 amp breaker is sufficient for 4500 watt water heater, except when applying the 80% safe maximum used to calculate loads today.
20 amp breaker x 80% = 16 amp maximum ...; which means 20 amp breaker is undersized slightly.

30-amp 3-way switch (SPDT switch) can be added to the circuit so you can toggle 240 volt water heater to 120 volt.
Works for ordinary residential water heater, but not heaters with electronic circuit board, electronic thermostat, This means the diagram will not work for tankless, heat pump, energy smart etc.
Reducing to 120 volt reduces heat time by a factor of 4, so typical tank will heat 4+ gallons per hour at 120 volt ....  gives you some hot water and more generator capacity to run lights, water well pump, grandpa's oxygen machine etc.
Adding a 30 amp SPST switch to either wire going to water heater will let you turn off heater completely.
Caution: You can toggle any time when generator is running as long as generator loads are relatively balanced.
Balanced load: a residential generator produces two out-of-phase 120 volt legs, with 240V potential across both legs. If you draw too much power off one leg, it causes disturbance in the magnetic field around the generator, and alters the waveform of electricity ... which can affect electronic devices inside house, and overheat generator.
All 240 volt loads are automatically balanced because they draw from both legs, but imbalance occurs when pulling power off 1 leg.
If you want to use the 120 volt strategy, set up your balanced generator loads to accommodate the change, usually within a range of 80% watt rating of generator.
Buy SPST:
Leviton 3032 30 amp switch at Amazon
Leviton 30 amp switch at Amazon
30 amp switches at Amazon

3-way switch wiring

DPDT switch wiring
Image below shows best way to toggle water heater from 240 volt to 120 volt
Works any time, not just when the generator is on.
If your transfer switch does not have 30 amp breakers it is no problem if you're connecting 120 volt, but IS a slight problem for 240 volt  ... UNLESS you change elements to 3500 watt,  in which case water heater will work fine with 20 amp.
The math: Volts x amps = watts.
4500 watt element divided by 240 volt = 18.75 amp
So technically a 20 amp breaker is sufficient for 4500 watt water heater, except when applying the 80% safe maximum used to calculate loads today.

20 amp breaker x 80% = 16 amp maximum ...; which means 20 amp breaker is undersized slightly. 30-amp DPDT 3-way switch with center off solves all the problems with imbalance, toggling between voltages, and turning off heater entirely. Bang done right.
But this design takes more breaker spaces in the transfer switch and requires dedicated 30 amp breaker in the main panel.
Works for ordinary residential water heater, but not heaters with electronic circuit board, electronic thermostat. This means the diagram will not work for tankless, heat pump, energy smart etc.
Buy double-pole double throw 30 amp
2 DPDT switch with center off 
2 DPDT switch with center off

Resources:
30 amp switch controls water heater
How to change 240V water heater to 120V
Figure volts amps watts
How to wire 240 volt outlets
Generators
What is 3-phase
wire transfer switch
30 amp DPDT switch

For certainty, always Test switch terminals using continuity tester before wiring.
24 amp safe maximum
Toggle water heater between 120Volt and 240Volt
30 amp 2 pole DPDT switch with center off
Use diagram that comes with device. Diagram shown might be different from your switch. Check terminals for continuity using multimeter.
120 volt Hot and Neutral connect to A1 A2 in either order, or you can connect to B1 B2. Water heater must be connected to L1 L2
Max 4500 watt non-simultaneous water heater
Use 240Volt when electric prices are lower, and faster recovery is needed. Use 120Volt during peak prices when less hot water is used
Buy
2 DPDT switch with center off
Buy Multimeter

Connect 120Volt wires as Hot and Neutral. Black connects to 120Volt circuit breaker and White connects to neutral busbar.
Connect 240Volt wires as Hot1 and Hot2. Both wires connect to 240Volt breaker.

Double pole double throw 30 amp switch
Buy DPDT 30 amp switch w center off
2 DPDT switch with center off at Amazon
2 DPDT switch with center off at Amazon
30 amp switches 30 amp double-pole 30 amp DPDT Ordinary 15-20 amp switches 15 amp pilot light
switch
Cooper 30 Amp switch
Single-pole/ 2-pole on-off switches
Buy:
30 amp 2-pole switch
30 amp industrial grade

Heavy duty double-pole switches to turn off both hot wires in 240 volt circuit
Buy:
30 amp motor switch
40 amp motor switch
Double pole double throw 30 amp switch
Buy:
30 amp DPDT switch

Resource:
Use this switch to toggle water heater between 120-240 volt
single-pole switch
Ordinary 15-20 amp toggle switch
Buy:
15 amp switch
20 amp switch

Indicator light shows when Load is ON
Buy:
Pilot light switch
Resource:
How to wire pilot light switch
Risk to motors and HVAC from generator
Generator can cause low voltage and phase fluctuations.
The problem of low voltage and phase fluctuation (lower voltage on one wire and not the other) do not affect resistance loads like light bubs or electric water heater, except to make them burn at dimmer capacity.
However low voltage and phase fluctuations do affect inductive loads like contactors, relays, motors, pumps, HVAC causing problems such as chatter on contactors and relays, and lower rotation speed on motor, causing higher temperatures, and burning out the motor or shortening motor lifespan.
voltage monitor
Larger image
IMC492 Single-phase Voltage monitor
Household power 120-240 volt is single phase.
Voltage monitor Protect motors and equipment from low voltage.
Adjustable voltage range
Caution: select monitor voltage to match incoming Line voltage
Select amp rating of contactor to match amp rating of Load (motor, pump etc)
Select matching contactor voltage and coil voltage range
Undervoltage on contactor coil will cause chattering and malfunction, Overvoltage on coil will melt coil.

Buy:
Single phase 95-270 volt range
3-phase 80-300 volt range
ICM phase monitor
Siemens monitoring relay

Resources:
Fuseholders
Contactors
Surge protector
Difference between surge and ground
Difference between single phase and 3-phase
IMC492 manual
Siemens .pdf


Locking plugs
Locking plugs/ twist lock
Nema L5 (look at bottom of graphic for Nema category) is same configuration for 20P or 30P/ use for 15, 20 or 30 amp
Nema  L6 is same configuration for 20P or 30 P/ use for 15, 20, 30 amp
Nema  L14, 4-pole is same configuration for 20P or 30P/ use for 20 or 30 amp
125 volt 3-wire has silver, brass and green screws
250 volt 3-wire has brass, brass, and green screws

Buy:
Leviton 2611/ 125 volt/ 15-20-30 amp/ 3-pole
Leviton 2621/ 250 volt/ 20-30 amp/ 3-pole
Leviton 2711/ 125-250 volt/ 20-30 amp/ 3 pole

Resources:
Locking plug Wiring diagrams
wiring inside transfew switch
Image: Bill R
Wire 240 Volt outlet Resources
How to wire 240 volt outlets
Cooper 30 Amp switch Water heater can be controlled directly with 30 Amp switch.
Use green color-coded 30 Amp switch and & 10 gauge wire.

Buy 30 amp switches:
30 amp switches
30 amp single pole switch
30 amp double pole switch
30 amp 3-way switch
30 amp switches at Amazon

Resource:
Control 240 volt with switch
Double pole double throw 30 amp switch Toggle water heater between 120 volts and 240 volts
Use DPDT 30 amp with center off
Ordinary 30 amp 3-way switch will do same job, but without center off
Slower heating during peak electric pricing can save money where hot water is still needed during peak pricing.

Buy double-pole double throw 30 amp
2 DPDT switch with center off at Amazon
2 DPDT switch with center off at Amazon

Resources:
How to convert water heater to 120Volts
See wiring diagram
See off-peak water heater options
elements
Elements

Contactors/ relays

Z-wave/ wifi
Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Install and troubleshoot garbage disposal Waste King disposal
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook