How to wire 3-phase outlets and surge protection

Cooper brand outlets
Intermatic brand surge protectors
Wire color codes at Wikipedia
3-phase wiring
Electricians forum
Engineering toolbox
Estimate line-to-line voltages
3-phase electric meters
3-phase motor wiring diagrams
Formulas for 3-phase
Line-to-line voltage = line to neutral x √3
3-phase has 2 varieties: 3-wire: three hot wires and no neutral, and 4-wire: three hot wires and a neutral

Types of phase wiring
3-phase wiring
Larger image
277 480 Three Phase WYE

480 volts across line-to-line

277 volts line-to-neutral


All Wye connections provide two voltages due to the common point or neutral connection.

Line-to-line voltage = 480V
Line-to-neutral voltage = 277V
277 Volt x √3 = 479.778 Volt

√3 = 1.7320
Voltages are higher or lower based on windings inside the transformer.
Power is generated at plant by rotating 3 coils in a magnetic field => power is sent out on 3 lines => power travels over wires to local area => power lines are connected to transformer => power is changed into specific voltage depending on which transformer is installed, and how the transformer is wired.
WYE or Delta configuration refers to how the 3-phase transformer coils are wired.
Inside each transformer are two coils: Primary coil is connected to power generation side. Secondary coil is connected to service wires that feed the service panel and circuit breakers.
If secondary coil is wound in WYE, then power to the service panel will always have a neutral, and two voltages.
Read
3-phase wiring
Larger image
277 480 Three Phase WYE

480 volts across line-to-line

277 volts line-to-neutral

Shows equipment ground
277 480 3-phase WYE
Use AG4803CE surge protector

Larger image
Three Phase 480V

480 volts across line-to-line

No system ground

Shows equipment ground
480 3 phase delta
Use AG4803D3 surge protector
Three Phase 480V delta corner ground

480 volts across line-to-line
3-phase wiring
Larger image
120 208V 3-phase wye

208 volts across line-to-line

120 volts line-to-neutral
3-phase wiring
Larger image
120 208V 3-phase wye
3 phase 4 wire
 
208 volts across line-to-line

120 volts line-to-neutral

Shows equipment ground
120 208 3-phase wye
Use AG2083C3 surge protector
120 208V 3-phase wye
Intermatic AG208C3 Surge
208 Volt 3-wire delta
3 Phase 3 wire 208 No Neutral

Phase to phase 208V
3-phase wiring
Larger image
347 600V three phase wye

600 volts across line-to-line

347 volts line-to-neutral
3-phase wiring
Larger image
347 600V three phase wye

600 volts across line-to-line

347 volts line-to-neutral

Shows equipment ground
347 600 3 phase wye
Use AG65033 surge protector
347 600V three phase wye
Intermatic AG65033 Surge Protection
How to wire 600 volt outlet
Larger image
Three Phase 600V

600 volts across line-to-line

No system ground

Shows equipment ground
How to wire 240 volt outlet and plug
Larger image
Three phase 250V

250V across each line

No ground
240 Delta 3-phase
Use AG2403D3 surge protector
High leg DeltaHigh leg delta   120-240 High leg Delta
Intermatic AG2403C3 surge protection

Black Line to Black Line 240V

Black Line to Neutral 120V

Red or Orange Line to Neutral 208V
120 240 high leg delta
Use AG2403C3 surge protector
240-480 High leg Delta

Phase to phase 480V

Phase A Phase C to Neutral 240V

Phase B high leg to Neutral 415V

Voltages are doubled compared with 120-240 high leg
High leg deltaImage shows Delta primary coil and High-leg delta secondary coil inside transformer
Read about transformers
Primary coil (or winding) is connected to power generation side.
Secondary coil is connected to service wires that feed the service panel and circuit breakers.

Configuration shows Delta primary coil. And High leg delta secondary coil.

If secondary coil inside transformer is wound in Delta configuration, there is no point where equal potential can be made between line and neutral.
The midpoint winding S3 is tapped which gives 120V or 208 volt to line.
S1 and S2 cannot carry any 120Volt loads.
As a result, the S3 coil is used for all 120Volt loads, plus 1/3 all 3-phase loads, causing potential imbalance.
120Volt loads must not exceed 5% Kva
The wild leg, or Leg B, or Phase B, is illustrated as Secondary B, and is marked with orange dot since the orange wire connects to this leg

Read
How to wire 480 volt outlet and plug
Larger image
277 480 Volts Single phase

With equipment ground
277 480 single phase
Use AG48013 Surge protector
277 480 Volts Single phase
Intermatic AG48013 Surge
Household wiring
120volt single-phase and 240 Volt split-phase

Intermatic IG1240RC3
Whole house surge
Larger image
Intermatic IG1240RC3 whole house surge protector/ pdf
Protect your business/ Protect circuit breaker panel and 120V and 240V circuits/ protect your tankless water heater, and any water heater with electronics
Installed directly into circuit breaker panel/ Replaced after each event
Protects circuit breakers, main panel, electric wiring, electronics, appliances
Does not protect TVs connected to sattellite dish/ for TVs use surge protector with co-ax TV connector
Household wiring

120 240 single phase
Household wiring

120 volt single phase

How to wire 3-phase timer

3-phase timer Buildings with 3-phase power also have Neutral wire used to power ordinary 120Volt outlets.

1) Use 120 Volt timer.

2) Install 3-pole contactor with 120Volt coil

3) Timer controls 120Volt coil.

4) 3-pole contactor turns 3-phase power ON-andOFF.

Examples of this timer:
Intermatic EH10 7-day programmable
Intermatic T101 24-hour analog
Repeat cycle timers
Dawn-dusk timer
365-day programmable timers
277Volt 24-hr analog timer
3 phase tiimer Some timers have dry load terminals.

1) Timer clock is 120 volt.

2) Timer relays are dry and receive no power from clock wiring.

3) This type of timer can be used to control 24Vac power from a transformer.

4) Install 3-pole contactor with 24Volt coil

5) Timer controls 24Volt coil.

5) 3-pole contactor points turn 3-phase power ON-andOFF.

Examples of this timer:
Intermatic GM series
Intermatic ET series


Example 3-pole contactor with 120Volt coil at Grainger

Example 3-pole contactor with 24Vac coil at Grainger

Example 3 & 4-pole 120Volt coil at Zorro

Example 3 & 4-pole 24Volt coil at Zorro

Example 3 & 4-pole 480Volt coil at Zorro

3-phase industrial timers

Additional links:

 EJ500 Utilitec Tork ST01C  ST01C ETW350 Aube T1032Aube Intermatic EI500Intermatic
    Water heater
GE  Leviton Hagar Westek TE06WHBWoods Sylvania

Timex
Intermatic Ei400 countdown timer Countdown
Intermatic parts
Intermatic trippers and parts
 Dayton Power pack
3-phase timer
3-phase timer
Sylvania timers
Tork timers and manuals
Tork TU universal timer
Paragon timers and manuals
Tork TU universal timer
Westek box timers

How to set analog  timers
Westinghouse timers
Westinghouse timers
Timex timers
Brinks timers
Gardena timers
Gardena T1030

Wire GE 15207 timer

GE box timers

Intermatic EH10 timer
EH10 timer
Intermatic T1906 and T1905
  
Intermatic T-101 T103 T104
Intermatic EH40 and WH40
  
Troubleshoot intermatic
Intermatic sprinkler timers
Intermatic pool timers and manuals
Intermatic T104P201
Intermatic timers
Intermatic GM series
How to wire Tork DTU40
Tork-DTU40
Intermatic GM series
How to wire Intermatic GM40

E-mail: info@waterheatertimer.org
Site map