Reset FV Sense lockout on Effex Water Heater
AO Smith, American, State, Lochinvar, Kenmore and other brand names carry same high efficiency gas water heater model ... color and labeling vary, and sometimes the drain valve is plastic instead of brass, but the design and function are identical.
 
Use 6 wraps teflon tape
? White for water lines
? Yellow for gas lines

Buy:
Teflon tape at Amazon

Buy:
Pipe wrench at Amazon
Channel locks

Resources:
How to remove rusted element


Buy:
Knipex channel locks
Irwin pliers
replace anode rod
Inspect anode each 2-5 years
Anode rod prevents tank from rusting
Buy:
Anode rods at Amazon

Resources:
Replace anode rod
How to maintain water heater

Buy:
Impact wrench at Amazon

Resources:
Replace anode rod
How to remove short water heater nipple
Water pressure gauge

Pressure gauge/ attach to water heater drain valve
Pressure over 80 psi can damage water heater and household plumbing
Buy:
Water pressure gauge
Temperature-pressure gauge

Resources:
Identify water heater valves
Troubleshoot water pressure
Automatic water heater shut off valve
Prevent flood
Automatic water shut off valve
Buy:
Water detectors at Amazon
Automatic water heater leak shut off at Amazon
Resources:
Leaking water heater/ steps
Pressure reducing valve
Pressure reducing valve
Pressure over 80 psi can damage water heater and household plumbing
Buy:
Pressure reducing valve

Resources:
Identify water heater valves
Troubleshoot water pressure
Sharkbite pressure gauge
Sharkbite pressure gauge

Buy:
Sharkbite pressure gauge

Resources:
Water heater valves

Water heater circulation system

Buy:
Grundfos at Amazon

Resources:
How to install recirculation system
COLD side Sharkbite flexible water heater connector
COLD side Sharkbite flexible water heater connector

Buy:
Sharkbite water heater connection
Braided water heater line
Stainless steel flexible connection

Resources:
How to install electric water heater
How to install gas water heater
Leaking water heater
HOT side Sharkbite flexible water heater connector
HOT side Sharkbite flexible water heater connector

Buy:
Sharkbite water heater connection
Braided water heater line
Stainless steel flexible connection
Braided water heater line
Flexible water heater connection

Resources:
How to install electric water heater
How to install gas water heater
Leaking water heater
89T thermostat kit
Electric water heater thermostats
Thermostats stick melt and come out of calibration... replace thermostat
Symptoms: Cold water, uneven temperatures, reset tripping, TP releasing water
Buy:
Water heater thermostats at Amazon

Resources:
How to replace electric water heater thermostat
Add another thermostat to water heater
How to wire thermostats
Marathon water heater thermostats
Two water heaters
Troubleshoot electric water heater
Icon gas valve   
Gas water heater thermostats
If tank is overheating or not heating correctly, replace thermostat
Symptoms: Cold water, uneven temperatures, TP releasing water
Buy:
Gas water heater thermostats at Amazon

Resources:
How to replace gas water heater thermostat
Add another thermostat to water heater
Troubleshoot gas water heater
Can the Effex recover from FV event without replacing water heater? Generally yes.
The FV sensor will trip if it senses gasoline vapors in the air. It does not respond to other types of flammable vapors.
Research shows that gasoline is the most common cause of fire or explosion caused by water heater.
Note: FV Sensor does not prevent the ignition of flammable vapors, the FVIR System is designed to reduce the risk of flammable vapor-related fires.
The FV sensor can also fail due to dust, dirt, moisture or simple defective part.

FV sensor must be kept clean and cannot be exposed to water. Flooded water heater must be replaced. Water rising just above the FV sensor might also flood the combustion chamber forcing replacement of heater and not just replacement of FV sensor.

The FV sensor is located inside a compartment on front of heater as images show. Open the FV compartment located on front of Effex heater.... Test and replace the FV sensor. It might be faulty.

Buy:
Flammable sensor kit

Resource:
How FV sensor works
How to test FV sensor
Review Effex water heater
Effex service manual
AO Smith Effex water heaterReset procedure from 2019 service manual
Assuming the FV sensor is functioning, wires are not damaged
"Should the FV-Sensor of this water heater detect the presence of flammable vapors the following FV-Sense Reset Sequence must be entered into the Electronic Control Display.
NOTE: “BEFORE RESETTING THE FVIR SENSE IN THE ELECTRONIC CONTROL DISPLAY, THOROUGHLY INSPECT THE AREA AND REMOVE
THE SOURCE OF THE FLAMMABLE VAPORS”.
1. Manual reset is accomplished by first turning off the power to the water heater for at least 10 seconds.
2. Then, while pressing the two temperature adjustment buttons on the display, turn the switch on the gas control valve/thermostat to the on position.
All the display icons will start to flash.
Temporarily release both temperature adjust buttons and within 2 seconds, press both temperatures adjust buttons again until all the display icons are on steady.
Release the two temperature adjust buttons.
The system will clear the fault, perform a reset, and normal operation will be restored."
effex gas controlPower to heater can be turned off by unplugging unit from 120 volt outlet, or using the On-Off switch located on right side of gas valve, as illustration from product manual shows.

Gas control valve thermostatThe thermostat probe contains a thermistor and ECO (energy cut off). 
''Thermistors are thermally (heat) sensitive variable resistors. A change in water temperature changes the resistance (measured in ohms) of the thermistor. The gas control valve interprets change in resistance as a change in temperature and uses information to activate and deactivate call for heat."

ECO will trip if water inside Effex tank exceeds 180°F high limit. This will cause thermostat to shut off gas to burner.
ECO for Effex is single-use, and tripped ECO indicates the gas valve is non-functioning ... gas control valve must be replaced. Effex display monitor will blink ECO error.
The high limit of 180°F means Effex cannot be used to store solar heat that can reach 180°F, or higher given the issue of global warming.
Use a solar storage tank from AO Smith instead of Effex.
AO Smith gas water heater
AO Smith Effex Atmospheric
Larger image
Buy:
40 gallon AO Smith Effex
50 gallon AO Smith Effex
50 gallon Reliance high efficiency
AO Smith gas water heater
AO Smith Atmospheric
Buy:
AO Smith at Amazon
50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
30 gallon
30 gallon LP
Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Install and troubleshoot garbage disposal Waste King disposal
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook