How to wire Intermatic T1906
T1905
T1976
T1975
20 amp timers
120 volt, 240 volt, 480 volt
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
stranded wire
600 volt 12 ga Stranded wire ot THHN wire is good for conduit with multiple wires ... but stranded cannot be installed under screw terminals on outlets, switches, timers etc without risk ... of heat causing splayed strands ....that come loose ... and begin to arc. Connect stranded to short piece of solid copper wire, and attach solid to screw terminal. Do not solder residential or commercial wiring.

Project wire, extension cords, thermostat, bell and automotive wire are not rated for residential or commercial wiring. Only wire maked 600 volt can be used for permanent household wiring.
Buy:
Southwire 600 volt stranded wire
Rolls of stranded wire
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI
T1905 timer
T1905 120 volt
T1906 240 volt

Larger image T1905-6

SPST with NO NC contacts
20 amp
Power consumption: Max 5 watts
Same wiring applies to both T1905-6 series timer and T1975-6 series timer
Only difference between T1905-6 and T1975-6 is day skipper wheel on T1975-6

Buy timer:
T1905 series 120Volt 20 amp 1 Hp timer 
T1905 480 Volt timer 
T1906 series 208-240V 20 amp timer 

Resources:
T1905 manual
T1906 manual
T1900 series sell sheet
T1900HD series sell Sheet
How to replace Intermatic clock motor
All Intermatic timers and manuals
Troubleshoot Intermatic timers
Intermatic trippers and parts
Intermatic T1906
T1975 120 volt w/ day skipper
T1976 240 volt w/ day skipper
Large image T1975-6
Larger image T1975ER

SPST with NO NC contacts
20 amp
7-day skipper wheel
Power consumption: Max 5 watts
7-day skipper wheel

Buy timer:
T1975 series 120Volt 20 amp with day skipper 
T1975E 480Volt with day skipper 
T1975ER 480-Volt Time Switch 3R Outdoor Enclosure w/ day skipper 
T1976 series 208-240Volt 20 amp timer with day skipper 

T1075 skipper wheelResources:
T1976 manual
T1975 manual
T1900 series sell sheet
T1900HD series sell Sheet
Troubleshoot Intermatic timers
Intermatic clock motor Replacement Clock motor
Convert timer to different voltage by changing clock motor
Buy
125Volt WG730 motor 
208-240volt WG733 motor 
480V WG736 clock motor 
Replacement trippers
Buy
156T1950A Trippers
Wiring applies to both T1906 series timer and T1976 series timer


Normally Open turns on with timer settings
Normally Closed turns off with timer settings

Larger image
208-240Volt/ or 480 Volt
T1906 and T1976 control 240Volt Load
Same wiring applies to 208 thru 240Volt
NO terminal is normally open. NO turns 'on' with timer settings. This terminal used for water heater circuit shown on left.
NC terminal is normally closed. NC turns 'off' with timer settings.

Use 12 gauge wire for 20 amp timer

SPDT single pole, double throw.
Only one Hot leg is turned off.

Larger image
120 Volt
Same wiring applies to T1905 timer and T1975 timer Only difference between these two timers is the day skipper wheel on T1975

NO terminal is normally open. NO turns 'on' with timer settings. This terminal used for water heater circuit shown on left.
NC terminal is normally closed. NC turns 'off' with timer settings.

Timer turns off Black hot wire, so 120V water heater has no electricity when timer is off.

Wires at 120V water heater: Connect black-to-black and white-to-white wires at water heater.

T1905 controls 2 loads 120 Volt/ control 2 loads
Same wiring applies to T1905 timer and T1975 timer Only difference between these two timers is the day skipper wheel on T1975

NO terminal is normally open. NO turns 'on' with timer settings. This terminal used for water heater circuit shown on left.
NC terminal is normally closed. NC turns 'off' with timer settings.

For T1906 and T1975, White wire is Hot
For T1905 and T1975, White wire is Neutral
208-240V / or 480V control Two Loads
T1906 and T1976 control two Loads

Each Load is same voltage ranging from 208Volt to 277Volt
Neither Load is turned ON at same time. Either NO Load or NC Load is active, but not both same time.

Bare ground wires connect to green screw.
When using White wire to carry Hot, then add black tape to tell next electrician that wire carries voltage.

To control different voltages, use timer with dry terminals such as GM40.
Resource:
How to wire GM40
T1906 timer controls 2-speed pump
Larger image
208-240V/ control 2-speed pump

Low speed is connected to NC terminal, and then pump operates continuously in low speed until timer turns ON.
When timer turns ON, High speed turns ON.
Diagram applies for both 120V and 240V 2-speed pool pumps.
Always check pump voltage and wiring diagram located on nameplate
Other timers can be used for 2-speed pool pump:
Resource:

Intermatic GM40, GE 15207 series, T106 timer, Tork DTU40 timer
Pump operates continuously. Install another timer on White Hot-neutral line to turn pump ON-OFF
T1900 Heavy duty series
Larger image T1075EHD
Larger image T1905HD
T1905HD 125V heavy duty
T1975EHD 480V heavy duty

Wires same as shown above
With day skipper
24 hour timer
NO NC contacts
20 amp
Motor withstands surge up to 6000 volts

Long life under extreme conditions
96 trippers 15 minute increments
Permanent built-in trippers
Permanent manual override: Full ON or Full OFF
T1905HD

Buy
 Timer:
1906HD heavy duty 125 volt 
T1975EDH heavy duty 480Volt with day skipper 

Resources:
T1900HD series sell Sheet with wiring
T1975EHD sell sheet
Instruction manual
Same wiring as T1905 and 1975 shown above

Buy

T1975EHD 480Volt heavy duty captive trippers with day skipper 
T1905 HD 120Volt heavy duty captive trippers with day skipper 
Keep wires straight
Use solid copper wire
If wiring terminal or end of wire are covered with green, use emery board to clean terminal and sandpaper to clean wire.
Insdulation under screw plate
Larger image
Both wires MUST be same gauge
Straighten each wire
If wire is corroded or overheated, clean the end with sandpaper and wipe with cloth.
If wire has been melted, cut back and reattach, or replace wire.
Tighten screw very tight against copper wire

Use wire connector  
Push on wire connectors
Use push-on wire connectors
3 wires/ or different gauge wires
Join wires with wire connector or push-on connector
Run jumper to screw terminal.
Buy:
Push on wire connectors at Amazon
Red 3P connector (shown) for 10-14 gauge wire
Connector assortment
Resource:
How to select and install wire connector
Fire safety/ Do not put stranded wire under screw plate
Do not install stranded wire under screw.
Problem1: picture shows 2 different gauge wires under screw plate
Problem2: Stranded wire will expand and contract and come loose under screw plate, even if it is the only wire under the screw plate
Attach stranded wire and solid wire with wire connector, and run solid copper jumper wire to screw terminal
Take photo of wires before starting.

Resources:
Timer caught fire
Load ratings for Intermatic timers/ pdf


Larger image
10-3-wire
10-3-wire  12 Ga
10 gauge or 12 gauge?
Compare your wire with short pieces of 10 and 12 gauge wire from local box store

10 gauge for 30 amp breaker.
10 gauge wire can have black-white and sometimes black-red

12 gauge for 20 amp breaker
12 gauge will have black and white wires
.
Resources:
Match color code and amp rating for wire
Basic house wiring
Add black tape when White wire carries voltage (applies to 208 and 240V circuits)
With 120 and 277 Volt circuits, White wire is Neutral, and Black is Hot
With 208 and 240 circuits, both wires are Hot, and both wires carry voltage
Black tape on White wire identifies wire is Hot and not Neutral

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools
DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook