Method
A...
After the unit has been
off for at
least a minute, plug it in, turn on switch; within a few seconds,
depress both arrow buttons on controller, and hold them until the
left light begins to blink. Release them, and within a few
seconds, push those arrow buttons in the following sequence:
L/R/L/L/R/L/R/R. This should reset the controller.
Method B...
after FV event on AO Smith
1. Turn off power to water heater for 10 seconds.
2. Restore power to water heater.
3.
Within 10 seconds of restoring power, press the two temperature adjust
buttons simultaneously until the left (green) “Vacation” LED begins to
blink (approx. 5 second delay). Once the Vacation LED begins to blink,
release both buttons.
4. Again, within 10 seconds, press both temperature adjust buttons
simultaneously until
Vacation LED is on steady (approx. 5 second delay).
5. Release two buttons, the microcomputer will clear the FVS
lock-out and normal
operation will then be restored.