How to control IntelliChlor salt chlorine generator
How to wire IntelliChlor salt chlorine generator
How to wire IntelliChlor SCG power center
How to wire iChlor TM Salt Chlorine Generator
Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI

IntelliChlor salt chlorine generator

Buy:
IntelliChlor
Pentair IntelliChlor Acid Washing Kit

Resources
IntelliChlor power center 5209590/ pdf
IntelliChlor manual

''Note: Before acid washing, remove the calcium buildup in cell: Use a garden hose on the jet setting and spray directly into both ends of the cell. Most of this calcium buildup has a slushy consistency and will be blown out of the cell. Once the majority of the calcium has been removed, continue with acid washing which will be more effective since most of the calcium has been removed.''
Don emails:
We have the IntelliChlor Salt Chlorine generator, or iChlor generator
Our pool company didn't wire the iChlor generator like they say in the manual.
The install manual gives numerous warnings

CHLORINE GAS BUILDUP CAN OCCUR WITH IMPROPER WIRING:
"To reduce the risk of personal injury the iChlor TM Salt Chlorine Generator (SCG) Power Center must be installed on and wired to the load side of the time clock, electronically controlled switch, or relay load side, so that it will receive power only when the pool pump is on.
Otherwise, dangerous chlorine gas buildup can occur. The SCG should never be energized when the pool pump is OFF and water is not flowing through the unit." IntelliChlor manual warning page/ pdf

Internet says "chlorine is poisonous and swallowing or inhaling it can cause harm." ... " most frequent complaint headache, eye irritation, sore throat, vomiting ... more sever cases result in "asthma like symptoms, defects in pulmonary (lung) function test hat can be permanent in older people, healthy people effects can last months."

Gene responds:
All salt chlorine generators should be wired in parallel with pump, both on same circuit breaker, both routed through same timer.
... this is so the salt chlorine generator cannot turn on unless pump is operating ...

Don emails:
Do you know of specifics with the NEC (national electric code) that say it's an infraction if you do not hook up a particular device as the specific instructions provide? I do hope there is some verbiage about this. We're dealing with a number of problems with this pool company.
I guess these guys didn't crack the manual at all and don't know ANYTHING about this unit. They mounted it horizontally (instead of vertically), without the 12"-18" of straight pipe, and without the bypass, -when this system is capable of over 105 GPM. Ha! Anyway... well, yea, the plumbers and the electricians were the same guys.

Gene Responds:
The chlorine generator wired in parallel with pump is safety related ... and relative to the specific equipment being installed
... it does not fall under electrical code that I know of ... consult local electrician ...
The wiring might meet local codes, but probably not if the installers weren't licensed electricians.
That means somebody could come out and RED TAG your installation because it wasn't inspected...

If the installation was very unprofessional, and dangerous to you  ...
I would gauge this is better reported to local BBB or through small claims court.
Overall your complaint will probably have little effect unless damage or death resulted

Recommend you use Fig-1 illustration below to have another electrician do the job, and possibly deduct the cost from final payment to company you're dealing with... of course they could put mechanic's lien on your property and cause more trouble than it's worth.

Fig-1 illustration simplifies the wiring by adding details that are missing from the iChlor product manual that shows 'MC Escher' version of the installation as you noted in earlier email.
Why doesn't the salt chlorine manual clearly show the installation of the salt chlorine generator? Where is the 12-18" suppose to be?
It's a confusing manual that requires additional 5209590 installation guide that shows timer and IntelliChlor SCG power center transformer.
Fig-1 solves the problem hopefully.

Resources
IntelliChlor power center 5209590/ pdf
IntelliChlor manual

The timer and transformer part of Fig-1 are correct based on my understanding of timers and transformers (power supply) and wiring.
Ground wire not shown, but must be installed.
A proper ground wire must be continuous and connect to timer, iChlor transformer box, and motor.
Metal enclosures must be grounded, but plastic enclosures are not. The 24 V line does not require ground wire.


T100 series 40 amp outdoor timer
120 volt and 240 volt models
24 hour dial up to 12 on-off per day

Buy:
240 volt 24-hour repeat cycle timer
120 volt timer
Beige colored timer

Resource:
How to wire 240 volt series
How to wire 120 volt series
Compare box timers
DPDT timers
Control w/ Z-wave
Control with wifi
But wait........ Don's pool pump has built in timer... there is no stand-alone timer to wire into **
**As a safety measure against exposure to chlorine fumes, the timer ensures that salt chlorine generator is only able to operate if timer has turned pump ON .... so the chlorine goes into water, and does not get released into air,,,
so how do you wire the iChlor TM Salt Chlorine Generator safely without a timer ?

Don emails:
.... with the latest variable speed pumps and their built-in electronics, and pump has a built-in timer, there's no need for an external timer in that setup.
And this is what we have.
The electrical rough-in only included the sub-panel and 1 low-voltage transformer (for pool light).
But after they put the equipment in, we mentioned yea you guys didn't put the salt system in (it was a $1300 upcharge and we had already paid for it).
So after some time they did put it in but they just jumped the salt low voltage transformer from the same 15 amp breaker supplying the light transformer (actually they just did a pass-through at the first transformer can). The VSP is wired to its own dedicated 15 amp breaker.

Gene responds
So the installation does not have a timer ... now it makes sense why they wired it wrong (and probably why they 'overlooked' it during initial installation).

Safety footnote about pool lights:
-All pool lights should be LOW voltage ... 12-13-14 volt AC, 300 watt transformer is typically used for power supply ....
Buy: Pool light transformers.
-Never connect household 120-240 volt light to a swimming pool. Overhead lights and equipment that do not come into contact with water or any part of pool can be 120-240.
-Piping that goes through pump and filter and supplies water to pool should made of plastic to ensure that short circuit in equipment does not travel into water.
Don emails his solution:
I'm gonna put a current sensing relay (current sensing switch) on the pump circuit so that can switch the salt system.
I intend to use this current sensing relay to sense the pump circuit and relay the high volt line heading to the salt power center

current sensing switchGene responds.
My website is amazon affiliate, enter through the following link and purchase amp relay and other materials
Buy:
Amp relay/ CSS or current switch/ current transducer

Your plan seems solid. The current sensing relay is self-powered, and operates as single-pole switch. Check amp rating and range. The contact points are usually low amperage, and cannot be used to switch a pool pump etc, but can be used to switch voltage on-off to the transformer.
More expensive amp relays can be very reliable ... they are susceptible to magnetic interference from nearby inductive loads like motors, pumps etc ... and do not substitute for good-ole hardwired magnetic relays and mechanical timers.
Amp relays/ current switches/ current relays etc have flammability rating and can be installed inside electrical enclosure and come in contact with wires etc.

Note that cheap amp relays (current sensing switches), are unreliable.


Fig-2 shows wiring diagram for current switch

Intermatic enclosuresThe current switch and connections MUST be made inside metal or plastic enclosure that is rated for electrical.
Do not use homemade wood box or plastic kitchen box etc.
Buy:
Current switch/ current transducer
6 x 6 enclosures

Resources:
Enclosures and boxes

Current switches are installed on 1 Hot wire...
Only 1 of the 2 wires going to pump is put through the amp relay.
The relay turns ON when current of electrons start flowing through the wire going to pump.
If the circuit is 240v then either wire can be used.
With 120 volt, the black hot wire is used.

If both wires going to pump are put through the amp relay, then the reverse flow of electrons on each leg (each wire) cancels the other out, and relay remains in OFF position.
Surge:
Fig-3 shows how to add Type 1 surge protector directly to the equipment, without needing a circuit breaker.
The closer the protection is located to the electronic motor, the better it protects.

Multiple surge devices on one circuit are ok.

Type 2 is different than Type 1.
Type 2 surge requires circuit breaker and must be installed inside a breaker panel.
 ... best protection when Type 2 is located in a breaker slot nearest to source of power entering panel.... and Type 1 is installed at or near the pool equipment.

Buy:
PS3000 Type 1 Type 2 universal surge protection
Pool and spa surge protection

Resource
How to wire surge protector


GFCI
Circuit should be GFCI protected, for example using GFCI breaker.
Caution: only 1 GFCI per circuit.
Resource
How to wire GFCI circuit breaker

Ground:
Bond the panel to ground rod if code requires ... or if the conduit is metallic, the it works fine as a bond when conduit is run underground.

Resources
IntelliChlor power center 5209590/ pdf
IntelliChlor manual
Safe electric wiring
Wiring notes:
Metal boxes and conduit require grounding.

Boxes, enclosures, wires, conduit etc must be attached to structure.
Movement is major cause of wiring failures.
Use 600 volt solid copper wire (not stranded).
Always match wire and breaker size.
When possible, locate electrical equipment out of direct sun exposure. High heat causes degradation and early failure of electrical installations
Buy
Southwire

Resources
Color code for wire
Safe electric wiring
Don's experiences shows that the all-in-one pump is a less-than-best 'upgrade' offered by pump manufactures ... it is NOT right choice for professional pool installations, because the professional installers in this installation could not do the correct installation. There were evidently other problems, unclear what they were, but the complaint was not about total failure of equipment ... it seems the pump and lack of a timer were the curve ball.

The weakness of all-in-one pumps is clear to me because of my experience in the trades.
For example, if the electronics inside pump go bad due to surge caused by the pump start-up, high summer temps, moisture, nearby lightning strike, poor manufacturing standards etc, the entire pump needs to be replaced. There won't be any repair parts ... and this type of pump will cost more in long run, aside from the $60 savings not buying a timer.

It shows the strength of buying simple, reliable pumps that just pump water ... without need for electronics.
And shows strength of assembling a group of devices that handle specific jobs ... that can be replaced separately.

box timersResource:
Compare box timers
DPDT timers
Intermatic
Control w/ Z-wave
Control with wifi

http://waterheatertimer.org/pdf/IntelliChlor-salt-chlorine-generator-safety.pdf
http://waterheatertimer.org/WiOn-50054-controls-Hayward-HeatPro.html
http://waterheatertimer.org/pdf/Haywood-HeatPro.pdf

How to make freeze outlet
Control valve actuators using sonoff
Intermatic-freeze-controls-and-parts.html
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Type 1 and type 2 surge protection surge protection
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Install and troubleshoot garbage disposal Waste King disposal
Buy
Electronic parts

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems

Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook