Use only 600 volt wire. Lamp cord, extension cords are not rated 600 volt. Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional. 30 amp breaker use 10 gauge / 120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker. Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps. Buy: 10-2 gauge/ 30 amp 10-3/ 30 amp Southwire electric tools |
Yellow
12 gauge 20 amp 120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire. ... cannot be connected to 30-40 amp breaker. 1 Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps. Buy: 12-2 gauge/ 20 amp 12-3/ 20 amp NMB is house wiring UF is underground Rolls of stranded wire HOOK UP Wires |
White
14 gauge 15 amp 120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker. White/ #14 gauge wire, with ground ... 15 amp capacity. Safe maximum 12 amps. Buy: 14-2 gauge/ 15 amp 14-3/ 15 amp NMB is house wiring UF is underground |
50-60
amp breaker use 6 gauge / 240 volt 50 outlet can be installed on 50 amp breaker only Buy: 6-2 wire Southwire electric tools NMB is house wiring UF is underground |
40-50
amp breaker use 8 gauge / 240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only Buy: 8-2 wire Southwire electric tools NMB is house wiring UF is underground |
Copper ground wire. Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire. Generally ... use same size as other wire in circuit Buy: 12 gauge copper ground wire Ground wire Green ground wire Ground pigtails Ground rods/ ground clamps at Amazon |
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock. Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure. All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes. Movement, damage and deterioration are major cause of electrical failure. Buy: Non-metallic flexible conduit Power whip Armored cable Southwire armored cable cutter Pull boxes |
Electrical tools must be insulated. Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off. Buy: Electrician tools kits KLEIN TOOLS Tools kits IRWIN tools KNIPEX Telephone cable knife Low Voltage Mounting Bracket for Telephone |
Push-on wire connectors in place of twist-on connectorsBuy:Push on wire connectors Amazon Red 3P connector for 10-14 gauge wire Lever connectors for stranded wire at Amazon HOOK UP Wires |
Protect wiring from damage Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable. -Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15 Buy End cutting nippers at Amazon |
Electrically insulated tools When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point. Buy tools: KLEIN TOOLS Wire strippers at Amazon Electric Wire Stripping Machine Linesman pliers Utility knife at Amazon |
Multimeters Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire. Buy: Analog multimeter Multimeters at Amazon Klein multimeter Electric testers at Amazon Clampmeter for testing amp flow on line |
GFCI circuit breaker A GFCI circuit breaker will protect all boxes on circuit. Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment. White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel. Buy GFCI circuit breakers |
Push down 1" wide Push down breaker Plug-in breaker Buy single-pole: Choose from 15 to 60 amp Eaton CL series Siemens 15-60 amp Single-pole tandem breaker Tandem breakers |
Push down 2" wide Push down breaker Plug-in breakers Buy double-pole: Choose from 15 to 125 amp Choose from 15 amp to 200 amp Eaton CL series circuit breaker Siemens circuit breaker Double pole GFCI |
T104 mechanical timers
can be noisy -To quiet a noisy timer, you can sometimes install rubber washers behind the timer or install new clock motor. -Also disassemble and clean parts, adding a bit of white grease to metal gears -Change clock motor Buy: T104 clock motor T104 trippers White grease Resources: Pictures of disassembly of timer Noisy timer |
|
Clock motor has plastic gears Look for clock number |
T104
can usually be
repaired -The motor and trippers can be replaced - T104 is designed to be repairable. For example. the trippers are made of softer metal than the unrepairable on-off switch they push during each rotation around the dial. Inspect the impact point for wear ... add white grease. If the impact point where trippers meet the switch is worn down, then timer is no good. Otherwise replace trippers. Another example is the clock motor is replaceable and has plastic gears. The reset of the timer has steel gears. The plastic gears wear out before the steel gears. Clean the steel gears, add a bit of white grease, and replace clock motor. The enclosure (box) is standard for all Intermatic T100, EH, ET series timers. So you can snap -Other parts can wear out. For example using stranded wire, or loose wires can cause burned terminals that are not repairable. Buy: T104 mechanism to snap into existing enclosure Resources: Pictures of disassembly and repairs T104 repair parts Intermatic enclosures |
Check your voltage T104 and EH40 are both rated 240 volts. -Do not connect wrong voltage to EH40 T101 and T103 timers are 120 volt, replace with EH10 -The T104 is 240 volt ... you can check three different ways. 1) is the 240 volt clock motor WG1573, the 120 volt clock motor is WG1530 2) is the breaker a double? if yes then voltage is 240 volt. 3) Use multimeter and check for 240 volt across terminals 1 & 3 .... the basic standard is that voltage must be within 80% of rated value, or minimum 192 volts. Below 80% threshold, electrical designs do not function as expected. Overvoltage, or surge, cause equal problems for electrical systems. T104 is repairable after typical surge event, EH40 is not repairable, Buy: Multimeters Resources: Electrical resources on the site |
|
-Crossover wiring T104 has 5 terminals A 1 2 3 4 (terminal A is not used) EH40 has 6 terminals 1 2 3 4 5 6 /Line from Breaker T104 terminal 1 goes to EH40 terminal 1 & 3 T104 terminal 3 goes to EH40 terminal 2 & 5 /Load T104 terminal 2 goes to EH40 terminal 4 T104 terminal 2 goes to EH40 terminal 6 -EH40 will snap into the old T104 enclosure to save work -The T104 is a valuable asset to sell on ebay or keep in backup. Enclosure (box) and timer mechanism can be sold separately. Resources: How to wire EH40 How to wire T104 |
Use only 600 volt wire. Lamp cord, extension cords are not rated 600 volt. Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional. 30 amp breaker use 10 gauge / 120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker. Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps. Buy: 10-2 gauge/ 30 amp 10-3/ 30 amp Southwire electric tools |
Yellow
12 gauge 20 amp 120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire. ... cannot be connected to 30-40 amp breaker. Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps. Buy: 12-2 gauge/ 20 amp 12-3/ 20 amp NMB is house wiring UF is underground Rolls of stranded wire |
White
14 gauge 15 amp 120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker. White/ #14 gauge wire, with ground ... 15 amp capacity. Safe maximum 12 amps. Buy: 14-2 gauge/ 15 amp 14-3/ 15 amp NMB is house wiring UF is underground |
50-60
amp breaker use 6 gauge / 240 volt 50 outlet can be installed on 50 amp breaker only Buy: 6-2 wire Southwire electric tools NMB is house wiring UF is underground |
40-50
amp breaker use 8 gauge / 240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only Buy: 8-2 wire Southwire electric tools NMB is house wiring UF is underground |
Copper ground wire. Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire. Generally ... use same size as other wire in circuit Buy: 12 gauge copper ground wire Ground wire Green ground wire Ground pigtails Ground rods/ ground clamps at Amazon |
Armored cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure. Non metallic flexible cables must carry ground wire, but does not have hazard of short circuit causing injury from shock. All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes. Movement, damage and deterioration are major cause of electrical failure. Buy: Armored cable Southwire armored cable cutter Non-metallic flexible conduit Power whip Pull boxes |
Electrical tools must be insulated. Always best to disconnect power, but issues of insulation failure, lack of proper grounding, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems pose a risk to anyone working on electric power. Buy: Electrician tools kits Klein tools Tools kits |
12 ga Stranded wire is good for conduit with multiple wires ... but stranded cannot be installed under screw terminals on outlets, switches, timers etc without risk ... of heat causing splayed strands ....that come loose ... and begin to arc. Connect stranded to short piece of solid copper wire, and attach solid to screw terminal. Do not solder residential or commercial wiring. Buy: Rolls of stranded wire |
Protect wiring from damage Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable. -Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15 Buy End cutting nippers at Amazon |
Electrically insulated tools When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistances and heat on wire and creates possible weak point. Buy tools: Wire strippers at Amazon Linesman pliers Utility knife at Amazon |
Multimeters Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire. Buy: Analog multimeter Multimeters at Amazon Klein multimeter Electric testers at Amazon Clampmeter for testing amp flow on line |
Buy Electronic parts Industrial supplies Tools and home improvement Home and garden Hayward pool Pentair pool Southwire electric |
|
Buy
Tools DEWALT Black and Decker Stanley SKIL Makita Porter-Cable Bosch Irwin Hand tools Klein hand tools Fluke electrical testing Dremel hobby tools Campbell Hausfeld air powered Tekton automotive Powerbuilt automotive Saws and saw blades |
|
Resource: Compare box timers DPDT timers Intermatic Control water heater w/ Z-wave |
|
Resource: Intermatic control centers: and parts Digital control centers and parts Tork control centers and parts Subpanels All control centers and parts Enclosures |
|
Resource: Programmable timers Countdown timers Off delay timers On delay timers Timer modules Din rail Twin & one-shot Woods Intermatic Tork |
|
Recirculation systems |
Buy
from my affiliate links every time/ thanks: Amazon As an Amazon Associate I earn from qualifying purchases Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission E-mail: geno03245w@gmail.com My response might end up in spam folder, check email folders Waterheatertimer on Twitter Message thru facebook |