Island sink gurgling water
Under sink vent not working.

E-mail: geno03245w@gmail.com
Kitchen sink requires minimum 2 DFU
Washing machine 2 DFU
3 DFU is enough vent for 1 toilet + 1 sink + 1 tub-or-shower
How to to install VENT under sink
Question about vent not working: 
Island sink gurgling water
Under sink vent not working.
The new kitchen remodeling put the sink and disposal on an island with no possible way to vent without air admittance valve (AAV). 
There is a double sink with 1 P trap and a Tee that connects both sink bowls. 
There is 6 DUF AAV vent installed between P-trap and where pipe enters wall.
When I run my disposal, it blows air up out of the other bowl and I get septic smell.
What can I do to fix problem?
Answer
The sink probably shouldn't be on an island, and maybe your experience will help others with similar remodeling plans.
With a double sink, a single P trap is code, but there are other issues.
First of all, the AAVs (air admittance valve) will respond to air pressure in the line. But does not function like a normal through-the-roof-vent that also allows air to escape the drain line.
Negative pressure (when air is drawn into pipe) and the AAV lets air into the drain line.

But when the drain is full of water and moving toward the AAV, it pushes a column of air in front of the water, creating positive pressure. The AAV shuts off when there is positive pressure.
The air has nowhere to go ... it cannot push up through an open vent to the roof and get released into atmosphere like normal ... instead the air creates blockage, causing a back up and gurgling into the other sink bowl.

Once the column of water passes the AAV, it will begin draw air into the pipe from the AAV, and the water should be able to flow normally.
If the drain is not letting water flow as quickly as normal vented sink, it can eventually cause line to get blocked with garbage.
Suggestions for island vent not working:
- Experimenting with different behaviors might help.
-If the drain line is not full of water, the AAV works fine. 
-So maybe there is too much water being used when the disposal is running. Reduce the water flow.
-Cut up less garbage and increase water flow. It will take longer each time, but long term result will probably be better.
-To make sure all garbage is getting flushed completely out of the line, run water into the drain for a while after each use.

Also consider following actions in this order: 
- Blockage: Take apart the tubular plumbing under sink to check if there is constriction. 
- Use drain cleaner and run water.
- After repeated drain cleaner, fill both sinks several times and let drain to try and flush out line. Repeat each week.
- Higher level of DUF for the AAV ... use 20 DUF instead of 6 DUF ... might help

- Larger 2" schedule 40  drain and trap up to the point where AAV is located ... this will increase pipe capacity ... then hopefully the drain line and AAV will give better result.

- You don't say it the tubular drain lines are 1-1/2" slip joint typically found in residential construction .... or a larger size 2" schedule 40 PVC drain typically found in commercial installations. The commercial size drain is solvent welded (get one with a clean out) and probably should be a requirement for island installation and might solve problem.
- Install 2" PVC trap and drain instead of using 1-1/2 tubular (likely available at plumbing supply)
- If your kitchen has access from underneath, say from the basement or crawlspace etc, check if the drain line drops straight down into a 3" pipe ... getting the kitchen drain into a larger pipe as soon as possible will improve flow.
Buy:
2" P trap
Oatey sure ventOatey vent
Oatey sure vent 6 DFU approved for drains up to 2" diameter
All in one vent for under sink
Approved to drain pipes up to 2"

Buy: sure-vent air admittance valve:
1 piece vent and tubular adapter
1 piece vent and tubular adapter
Oatey 39225
add a ventLarger image...
Add sure-vent to P-trap
P-trap goes through wall
Oatey meets code requirement: Minimum 4" space between horizontal pipe and vent
Oatey 3925 rated 6 DFU/ Oatey 6 DFU vent specification sheet
Vent must be located at least 2 pipe diameters away from trap weir
Buy:
Oatey sure vent with tubular adapter
Sure vent with tubular adapter
Sure vents at Amazon

Buy: other parts:
P-traps and trap adapter
S-traps
Quick vent or sure-vent at Amazon
1-1/2 tubular drain pipe
PVC slip joint Tees at Amazon
PVC slip joint elbow
Washers
Tee
90° elbow
Slip joint extension
T plus 2 thread sealant at Amazon

 'Trap weir' is the final bend in trap as water exits trap Read more
Oatey vent
Oatey sure vent
6 DFU

Approved to vent pipes up to 2"

Best air admittance valve:
1 piece vent and tubular adapter
1 piece vent and tubular adapter

Resource:
Oatey 6 DFU .pdf
Connect to tubular sink drain

Resource:
Oatey 6 DFU spec sheet
Oatey sure vent 20 DFU
Oatey sure vent
20 DFU

Approved to vent pipes up to 3"

Best air admittance valve:
Admittance valve 20 DFU vent

Oatey sure vents are 100% closed if they fail... so never sewer gas odor. Glue to 1-1/2" or 2" PVC

Resource:
Oatey sure vent installation

sure vent wall box
Sure vent wall box
So vent can draw air

Buy louvered access box:
Oatey sure vent wall box
Oatey access panels
Louvered access required for inside-the-wall sure vent

Sure vent requires open access to air; to draw air, and for visual inspection, and for replacement
tubular drain pipes
Buy Extra tubular parts
Tubular drain pipe
Flexible coupling
1-1/2 to 1-1/4 connector
Chrome flexible drain pipe

Buy
T plus 2 at Amazon
T plus 2 with applicator brush
Apply to each washer for first-time, no leak tubular drain pipe assembly.
Messy but good. Keep off clothes, and wipe hands to prevent getting it all over everything.
Does not dry out in can.
1/4 pint: handy size for DIYers


fixture unitsFixture units
National plumbing code
fixture units
Support the economy:
Buy water heaters from my associate links:

50 gallon Gas water heaters at Amazon
40 gallon gas water heaters at Amazon
50 gallon Electric water heaters at Amazon
40 gallon electric water heaters at Amazon
Hybrid / heat pump/ water heaters at Amazon

Resources:
How to install gas water heater
How to install electric water heater
Troubleshoot gas water heater
Troubleshoot electric water heater
Point of use water heaters
Resources:
Troubleshoot Gas valves with manuals
Icon gas valve

How to replace water heater element Waste King disposal
How to wire tankless electric


Install point of use water heater
Titan tankless

Contactors/ relays
Install and troubleshoot garbage disposal Waste King disposal
Programmable timers

Woods timers
surge protection
Anode rods anode rods
Recirculation system

Tankless recirculation
Point of use water heater
Type 1 and type 2 surge protection surge protection
Buy
Industrial electric

Industrial supplies

Tools and home improvement

Home and garden

Hayward pool
Pentair pool

Southwire electric
Buy
Tools

DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades
box timers Resource:
Compare box timers
DPDT timers
Intermatic
Control water heater w/ Z-wave
Intermatic control centers Resource:
Intermatic control centers: and parts
Digital control centers and parts
Tork control centers and parts
Subpanels
All control centers and parts
Enclosures
programmable timer Resource:
Programmable timers
Countdown timers
Off delay timers
On delay timers
Timer modules
Din rail
Twin & one-shot
Woods
Intermatic
Tork
Low voltage power packs Recirculation systems
Buy from my affiliate links every time/ thanks:
Amazon
As an Amazon Associate I earn from qualifying purchases
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook