Use only 600 volt wire.
Lamp cord, extension cords are not rated 600 volt.
Use copper wire only. Aluminum wire is fire risk and should be avoided or installed by professional.

30 amp breaker use 10 gauge /
120-240 volt 30 amp outlet can be installed on 30 amp breaker only/ use 10 gauge wire ... cannot be connected to 15-20-40 amp breaker.

Orange/ #10 gauge wire, with ground ... 30 amp capacity. Safe maximum: 30 x 80% = 24 amps.
Buy:
10-2 gauge/ 30 amp
10-3/ 30 amp
Southwire electric tools
Yellow 12 gauge 20 amp
120 volt 20 amp outlet can be installed on 20 amp breaker, but not 15 amp breaker/ use 12 ga wire.
... cannot be connected to 30-40 amp breaker. 1

Yellow/ #12 gauge wire, with ground ... 20 amp capacity. Safe maximum 16 amps.
Buy:
12-2 gauge/ 20 amp
12-3/ 20 amp

NMB is house wiring
UF is underground
Rolls of stranded wire
HOOK UP Wires
White 14 gauge 15 amp
120 volt 15 amp outlet, AFCI, GFCI, timer, switch etc can be installed on 15 or 20 amp breaker. Never connect 15 gauge wire to 20-30-40 amp breaker.

White/ #14 gauge wire,  with ground ... 15 amp capacity. Safe maximum 12 amps.
Buy:
14-2 gauge/ 15 amp
14-3/ 15 amp

NMB is house wiring
UF is underground
50-60 amp breaker use 6 gauge /
240 volt 50 outlet can be installed on 50 amp breaker only
6-2 wire
Buy:
6-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
40-50 amp breaker use 8 gauge /
240 volt 40 amp outlet can be installed on 40 or 50 amp breaker only
6-2 wire
Buy:
8-2 wire
Southwire electric tools
NMB is house wiring
UF is underground
     
Copper ground wire.
Every device, load, metal enclosure etc must be grounded. Ground wire must be continuous throughout installation, never switched on-off, never used as a Neutral wire.
Generally ... use same size as other wire in circuit
Buy:
12 gauge copper ground wire
Ground wire
Green ground wire
Ground pigtails
Ground rods/ ground clamps at Amazon
armored cable
Non metallic flexible cables must carry ground wire, but do not have hazard of short circuit causing injury from shock.

Armored steel cable can be used as a grounded connection, and will protect wires from damage. Metal can be energized from an insulation failure.

All conduit ...metal, plastic ... flexible and rigid ... must be attached to structure, and attached to enclosures, boxes.
Movement, damage and deterioration are major cause of electrical failure.
Buy:
Non-metallic flexible conduit
Power whip
Armored cable
Southwire armored cable cutter
Pull boxes
Southwire armored cable cutter
Electrical tools must be insulated.
Always best to disconnect power, but insulation failure, lack of proper grounding, grounded neutral, lack of GFCI, out-of-code wiring, generator operating without transfer switch, and other problems still pose a risk to anyone working on electric power ... even when breaker is off.

Buy:
Electrician tools kits
KLEIN TOOLS
Tools kits
IRWIN tools
KNIPEX

Telephone cable knife
Low Voltage Mounting Bracket for Telephone
Push on wire connectors

Push-on wire connectors in place of twist-on connectors

Buy:
Push on wire connectors Amazon
Red 3P connector for 10-14 gauge wire
Lever connectors for stranded wire at Amazon
HOOK UP Wires

Protect wiring from damage
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

-Code says: Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon


Electrically insulated tools
When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistance and heat on wire and creates possible weak point.
Buy tools:
KLEIN TOOLS
Wire strippers at Amazon
Electric Wire Stripping Machine
Linesman pliers
Utility knife at Amazon
multimeter
Multimeters
Voltage is tested across two separate wires. Ohms or resistance is tested across both ends of same wire. Amperage is tested along one or two points on same wire.
Buy:
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line

GFCI circuit breaker
A GFCI circuit breaker will protect all boxes on circuit.

Circuit must be grounded. Ground wire must be continuous and connected to each piece of equipment.

White wire on circuit breaker must be connected to Neutral busbar inside the breaker panel.

Buy
GFCI circuit breakers
Push down
single-pole breaker
1" wide Push down breaker
Plug-in breaker
Buy single-pole:
Choose from 15 to 60 amp
Eaton CL series
Siemens 15-60 amp

Single-pole tandem breaker
Tandem breakers
Push down
double-pole breaker
2" wide Push down breaker
Plug-in breakers
Buy double-pole:
Choose from 15 to 125 amp
Choose from 15 amp to 200 amp
Eaton CL series circuit breaker
Siemens circuit breaker
Double pole GFCI
T10404RIntermatic T10404R and T10101R control center
Two timers for pool filter and learner
T10101R comes with two 120 volt T101 timers
T10401 comes with two 240 volt T104 timers
Max 40 amp (safe max 32 amp). Rated for up to 5 Hp.
Resource: See charts for motors: amp, distance, wire size

T10000R series/ without breaker slots/
One knockout on the right side for mounting switching device or GFCI.
Two combination décor/toggle switch knockouts on the deadfront.
Numerous wiring knockouts located on bottom of panel.
This control panel has no circuit breaker spaces, but can install surface mounted circuit breaker or a din-rail mounted fuseholder. Multiple fuses and breakers on single circuit are OK. Multiple surge protectors OK on single circuit. Caution: only 1 GFCI or AFCI per circuit.
 Read information how to install and wire for 120 volt outlet/ switch

Buy:
PE10000 enclosure/ no timer/
T10101R with 2x T101  /120V
T10004R with one T104    /208-240V
T10404R with 2x T104  / 208-240V
T10604R with T106 and T104  /208-240V for 2-speed pumps
T12404R with T104201 and T104/   208-240V with fireman switch
Resources and manuals

T10000R series manual and sell sheet
T10404R door label
T10101R manual
T101M

Mechanism only
Use thumb spring located top inside timer to remove old mechanism from enclosure


Buy:
T101M 120 volt mechanism only
T101 series 120 volt timers
T104M 240 volt mechanism
T104 series 240 volt timers
T104M201 mechanism with fireman switch
T10404 wiringT10404T with two T104 timers for filter and cleaner
Supply voltage is 240 volts that connects to Terminals 1 and 2 on Filter timer.
Both timers have a clock motor that rotates the yellow dial once per day. The dial can have up to 12 sets of trippers for 12 ON-Off periods each day. Both clock motors are connected to terminals 1 and 2 on the Filter timer.

The terminals on Cleaner timer receive no voltage unless the Filter timer is ON. This assures that pool cleaner can only run when the filter pump is ON.

 Filter pump must be ON so debris from the pool can be run through the sand filter.



T10404 wiring    Fig 2 is same as Fig 1 shown above.
Note that both the Filter Pump and Cleaner must be same voltage, either 120V or 240V.
Timer clock voltage must match the Pump and Cleaner.
The clock motors can be changed to either voltage
Buy:
240 volt clock motor
120 volt clock motor

Both clock motors must connect to terminals 1 and 3 on Filter Pump timer.

The pool cleaner never operates unless the filter pump is running. The wiring is designed for that purpose, so that the debris picked up by cleaner gets sent through the sand filter.
T01404 wiringEach timer on different breaker/ 2 circuit breakers
Illustration shows a method for running the filter pump and cleaner on separate circuit breakers.
This came from an email question from a fellow who was experiencing overload on 1 circuit breaker, and wanted to install second breaker to run the cleaner.
The contactor turns ON when filter timer is ON. The contactor closes circuit so cleaner timer receives power. When cleaner turns ON, it is powered from the second circuit breaker.

Buy: 40 amp 240Volt contactor

Convert control center timers to either 120 Volt or 240 volt by changing clock motor
Buy:
240 volt clock motor for T10404R
120 volt clock motor for T10101R


Resources:
Contactor wiring
Match wire and breaker size

Resource:
T10101R manual
Match wire and breaker size
T10101R wiringT10101R 120 volt wiring
This control center has same function as T10404R except for 120 volt installations.

240 volt motors run more efficiently than 120V.
Most motors can be wired for either voltage. Look at rating plate on motor to select correct control center, wire size and breaker.

Buy:
T10101R control center with 2x T101  /120V

Convert control center timers to either 120 Volt or 240 volt by changing clock motor
Buy:
240 volt clock motor for T10404R
120 volt clock motor for T10101R
Resource:
T10101R manual
Match wire and breaker size


Add a freeze thermostat to T10404R


When temperatures drop below set point, the freeze override will send power to the Filter pump.
Power is also on the cleaner timer.
Intermatic freeze control PA102
Buy
PA102 mechanical thermostat and SPDT relay
Freeze control
Inline freeze switch/ 15 amps max

Resources:
How to wire PF1202T and PF1222TB
Intermatic freeze controls and manuals
Resource
How to make a freeze outlet
WH40 clock motorTroubleshoot T10404 and T10101R
-Flip circuit breaker fully off and then back on.
-Check that both clock motors are connected to terminals 1 and 2 on the Filter timer.
-Observe if both clock dials are rotating 1 revolution per day. If dials are not rotating, then clock motor is bad, unit is not getting voltage, or is getting incorrect voltage.
-Convert timer to either 120 Volt or 240 volt by changing clock motor
Buy:
240 volt clock motor for T10404R
120 volt clock motor for T10101R

-Check if each clock dial has ON and OFF trippers fastened to yellow dial.
-Move both override levers to ON position. If Filter pump is OFF and Cleaner pump is OFF, then move both override levers to ON position. If Filter pump works and Cleaner pump works, then voltage is correct and wiring is correct.
-If all the above steps function correctly, observe if the trippers push the override lever back and forth between ON position and OFF position. If the dial rotates tripper past the override lever, and override lever does not change position, then most likely problem is worn trippers need to be replaced.
Intermatic 156T1978A tripperBuy: trippers
156T1978A set 2
156T1978A trippers
PA115 - 25 sets<

-If the trippers are sliding past the override lever, and new trippers do not solve problem, then replace timer module.
Buy:
T101M 120 volt mechanism only
T104M 240 volt mechanism

- Undersized wire and breaker can cause malfunctions.
- Check that motor load is working correctly. Look at rating plate on motor for voltage and amperage requirements.
- Convert control center timers to either 120 Volt or 240 volt by changing clock motor
Buy:
240 volt clock motor for T10404R
120 volt clock motor for T10101R

-If the above steps check OK, then check terminal connections and wires. Max 2 wires under a terminals. Do not use stranded wire. Clean corroded wires with sandpaper, or use white vinegar to help dissolve build-up on terminals. Tighten screws very tight against copper wire. Use only copper wire. 


clean and straighten wire ends
Insdulation under screw plate
Larger image
Both wires MUST be same gauge
Straighten each wire 
Tighten screw very tight against copper wire



Larger image

Connect stranded and solid with wire connector and run jumper to screw plate. 
Or add solder to stranded wire to make solid.
See example image

ories, safe electric practice for boxes/ enclosures
For household 120-240 volt power:
-Use only approved 600 volt cables, wires, enclosures, boxes, conduit etc for household 120-240 volt.
-Extension cords are not rated 600 volt, and cannot be used for permanent in-wall wiring.
Resources Extension cord code
-Do not use makeshift, homemade boxes that are not rated for household voltage.
-Correct box must be used for application ... a light fixture or fan requires round or octagon box ... cannot use switch box, or square junction box for light fixture ... cannot use round, octagon, or square junction box for switch and outlet.
-All enclosures and boxes require a cover that is made to fit box, and must sit flat and tight against box.
-Missing knockout holes must be filled.
-Keep enclosure door or cover in place and closed to contain spark and potential fire hazard.
-Box cannot have vent holes or heat fan installed where air supply can feed a potential fire. 
-Never solder household wiring connections. High heat from resistance, caused when amperage gets pushed through the wire by voltage, will melt solder and cause potential hazard.
-Use only approved 600 volt wire connectors. Never reuse old wire connectors.
-All enclosures, wiring, conduit etc must be attached firmly to structure, and located so cannot be damaged by lawn equipment etc. and best if located away from high heat, exposure to sun. Heat will cause deterioration of electrical installations.
-Enclosures require ground wire to be present and connected to all devices, equipment etc. Metal boxes and enclosures require connection to ground wire. Plastic boxes do not require grounding.
Resources: Safe electric wiring/ for boxes and enclosures     Color code for wire

Low-voltage structural wiring (doorbell, communication, TV etc):
-Never include low-voltage 'structural wiring' inside same enclosure, conduit, raceway or box as household voltage.
-Low voltage structural wiring and household wiring must be electrically separated to prevent insulation failure from energizing low voltage wires, cause fire and safety hazard.
-Structural wiring can be run inside walls, does not require enclosure, box conduit etc except for installation convenience, weatherproofing, reliability, organization, access to splices and connections etc.
-Household 120-240 volt wiring cannot be soldered ... but low-volt structural wires can be soldered when needed.
Resource: troubleshoot low voltage doorbell

Multimeter
Test for breaks in wire/ Test for voltage
Most appliance require 80% rated voltage to function correctly
Buy
Analog multimeter
Multimeters at Amazon
Klein multimeter
Electric testers at Amazon
Clampmeter for testing amp flow on line
Resource:
How to test and replace element
How to test thermocouple
Element tests for 120 volts
How to test wire
Safety when testing wires:
Never touch wet or previously flooded appliance.
Never stand on wet surface when working on electric.
Never stand on bare soil, put down dry boards.
Tape tester leads to wood sticks to keep hands away from power.
Use non-contact voltage tester before touching wires.
Never touch or lean into any made of metal.
Remove metal objects from pockets.
Do not use oxygen or fuel accelerants in same room as electrical repairs

Resource:
Basic house wiring

Non-contact voltage tester
Test for power without touching connectors
NEVER assume power is OFF

Buy:
Non-contact voltage tester Amazon
Electric testers at Amazon
Resource:
How to test electric power is off
remove cable staple
Use nipper instead of pliers or screwdriver for removing staples (and nails). Do not damage cable or wires inside cable.

Code
-Cable SHALL BE secured without damage to the outer covering. NEC sec. 336-15
Buy
End cutting nippers at Amazon

 
linesman pliers

When removing insulation from wire, do NOT score or put cuts on surface of copper wire. Doing so increases resistances on wire and creates weak point.
Buy tools:
Wire strippers at Amazon
Linesman pliers
Pro linesman plier
Needle nose pliers
End cutting nippers at Amazon

Weather resistant plastic box for outdoor extension cord connections, Christmas lights, outdoor power strip etc . Not for connecting wires with wire nuts®, or in-wall wiring, but can be used indoors to organize extension cords, power strips etc.
Weather resistant is not weatherproof or watertight. Use enclosures rated IP65 and IP67 for waterproof.
Extension cords cannot be used for permanent wiring.
Buy:
Large-medium-small electric cord box
Socketbox
Raintight enclosures
Water-tight cord lock
Resource: Enclosures and boxes




Buy
Tools
Milwaulkee
DEWALT
Black and Decker
Stanley
SKIL
Makita
Porter-Cable
Bosch

Irwin Hand tools
Klein hand tools
Fluke electrical testing
Dremel hobby tools

Campbell Hausfeld air powered
Tekton automotive

Powerbuilt automotive
Saws and saw blades

Buy from my affiliate links every time/ thanks:
Amazon
''As an Amazon Associate I earn from qualifying purchases''
Enter Amazon from any link on my site, fill cart with any item ... purchases pay small commission

E-mail: geno03245w@gmail.com
My response might end up in spam folder, check email folders
Waterheatertimer on Twitter
Message thru facebook
>